background image

 

OPLC-2100 Operation Manual 

                                                                                                                                                                                  

CONFIDENTIAL

 

 

 

21 Harbor Park Dr. N, Port Washington Phone: 516.656.72211 Fax: 516.626.7201 

 

 

2. Operation Basics 

 
The OPLC-2100 controller (“” version) is designed to provide automatically regulated heat distribution by cycling a 
boiler  on  and  off  and  modulating  the  flame.  The  controller  continuously  calculates  the  amount  of  heat  requested  by  the 
building  taking  into  account  the  outdoor  temperature,  heating  system  temperature,  boiler’s  steam  pressure  and  selected 
settings.  Then  the  controller  assumes  that  this  requested  heat  value  is  actually  the  average  heat  amount,  which  must  be 
delivered to the building. Knowing the CYCLE setting the controller calculates the ‘ON’ part of the cycle  and controls the 
flame  modulation.  To  achieve  an  optimal  performance  of  the  heating  system  a  discrete  Proportional-Integral-Derivative 
(PID)  algorithm  is  implemented  in  the  “”  system.  Based  on  generic  control  loop  feedback  mechanism  the  PID 
controls flame modulation. 
     It makes sense to have some constant period of the boiler operation (CYCLE), which, in turn, is divided to ‘ON’ part of 
the cycle, during which the boiler is on, and the rest of the cycle, when the boiler is off (‘OFF’ part). In such a scheme of 
boiler operation the average amount of heat delivered to a building is proportional to the ratio of’ ON’ and CYCLE values. 
  In  brief,  the  controller  calculates  the  heat  amount  requested  by  the  building  (percents)  and  transforms  this  value  to  the 
parameters  of  the  boiler  cycle  (minutes).  Main  goal  of  the  PID  control  is  supporting  stable  value  of  the  boiler’s  pressure 
which  is define by pressure set point and three PID parameters. Controller attempts to correct the error between  measured 
pressure and desired pressure set point by calculating and then outputting corrective action (open or close ) to the boiler’s 
Gas Valve actuator.  Special sequence of the functionality for the “” is implemented to provide proper control of the 
boiler  during  the  ‘ON’  part  of  the  Cycle  (Fig.3).  The  flame  modulation  can  starts  after  the  certain  period  of  time  called 
“Purge” when Gas Valve position achieves special set point (called ‘LFR’ – Low Frame Rate) and after ‘Purge Delay’ set 
point.  Switch  from the ‘ON’  part of the cycle to the ‘OFF’ part of the cycle required  “Post Purge” period  which  includes 
time for moving Gas Valve from a point where it was during on the ‘ON’ part to the LFR set point and shat down the boiler. 
After  ‘Post  Purge  Delay’  the  Valve  returns  to  the  zero  position.  The  PID  control  is  active  on  the  Heat  Up  state  and  D 
(N):Norm state of the Heating Cycle (Fig.3). 
  

3. Controls

 

 

The four-button  keypad and  16 characters by 2 lines  LCD backlit display can be  found on the front panel of the 

OPLC-2100. These controls provide full local management of the system. Operator can read system status information (e.g. 
temperatures,  pressure,  cycle  parameters,  and  alerts),  set  the  operational  modes,  and  change  settings.  The  control  keypad 
consists of four pushbuttons: Escape (Esc), Down (

), Up (

), Enter (Enter). The keys are also marked with letters A, B, 

C, D to simplify the passwords memorizing. Holding down the (

) or  (

) keys will  speed up decrement  or increment of  

setting  parameters. 
 

Upper  line  of  the  display  shows  current  mode  of  operation  (AUTO,  MANUAL,  or  SET),  percentage  of  heat 

requested, and the operational status. Lower line is dedicated to show system status information and setup dialog. 
 

4. Menu

 

 

The process of interaction is menu driven. Menu chart is shown on Fig 2. The menu is organized in convenient and 

logical way, and follows a simple set of rules. 
 

 

The menu chart is organized as a set of menu boxes. To navigate between the boxes one should press 
Enter key to move to the right on the chart and Esc key to move backward. 

 

Each box contains one or more menu items. To switch between the items inside a box one should press Up 
or Down keys. 

 

Each item represents one menu entry: select a setting to change, enter a new setting value, change mode of 
operation etc. 
If the item contains "NEW" word then the new value has to be entered: Pressing Up and Down keys 
change the value. Pressing the Enter key accepts the new value. Esc key rejects the new value, and leaves 
the setting unchanged. 

 

If a password is required then one should enter a certain key sequence. For convenience the passwords are 
coded as a sequence of letters (e.g. DDBBCBA). 

 

Starting point of the menu is the topmost item of the leftmost box, which is a current cycle parameters line 
in the chart. If lost in the menu just press Esc repeatedly, until the display shows something like: 
"Cyc:29/61  ON:12”. You are now in the upper left corner of the menu chart.

 

Summary of Contents for OPLC-2100

Page 1: ...ccordance with operation settings and measured temperatures pressure to achieve optimal heating delivery and reduce fuel losses Figure 1 OPLC2100 Front view The OPLC 2100 features Adjustable Day and Night modes of operation Adjustable Winter and Summer modes of operation Programmable Heat Up and Cool Down set points Morning Boost period up to 120 min Provides compensator control for unusual weathe...

Page 2: ...m the ON part of the cycle to the OFF part of the cycle required Post Purge period which includes time for moving Gas Valve from a point where it was during on the ON part to the LFR set point and shat down the boiler After Post Purge Delay the Valve returns to the zero position The PID control is active on the Heat Up state and D N Norm state of the Heating Cycle Fig 3 3 Controls The four button ...

Page 3: ... Boost Span NEW BoostSpn 0 N Stbk 15 F SET BoostAdvance NEW Boost Adv 0 D ICutOff 70 F SET In D CutOff NEW D CutOff 70 N ICutOff 60 F SET In N CutOff NEW N CutOff 60 D_Band 2 5 F SET D_Band NEW D_Band 2 5 F InDoorTemp 90 F SET Day Begin NEW Begin 5 00am Heat Gain 4 0 SET Day End NEW End 10 00pm Comp Snstvty 1 0 SET WntrBegin NEW WrBeg Oct 15 Heat Limit 100 SET WinterEnd NEW WrEnd May 15 MotorType ...

Page 4: ...D_I 0 5 CAL ValveCloseP NEW Cadj 572 SampleRate 12sec SET PID_D NEW PID_D 0 2 PurgeDelay 30sec SET PurgeDelay NEW PurgeD 30sec PsPurgeDly 15sec SET PsPurgeDly NEW PPurgeD 20sec PSen 4ma 15psi SET Pressure Stp New Pres 5 6psi PSen 20ma 15psi SET LowFlame LVL NewFlameLvl 15 Pressure 4 9psi SET SamplingRate NewSampleR 12sec SYS Temp 120 F OD Temp 42 F Com ID 1 Fig 3 Typical track of the Fuel Valve po...

Page 5: ...onal State are permanently displayed in the upper line of the LCD as follows LCD Indicator Mode of Operation Upper line begins with Description Possible Operational States indicate on the right corner of the upper line OFF OFF PPrg Post Purge Auto AUTO hh AUTO max Calculated Target Heat Amount to be delivered hh in the range of 0 100 Summer D Mild N Mild D ICOFF N ICOFF N Stbk D Norm N Norm HeatUp...

Page 6: ... 1 Cyc 0 CL OFF CL 2 Cyc CL 0 ON CL Regular Cycle CL Cycle Length is A B in minutes A Calculated time amount the boiler must be On B CL A C Current minutes boiler is On or D Current minutes boiler is Off 0 heat to be delivered Boiler is OFF more then CL minutes 100 heat to be delivered Boiler is ON more then CL minutes sine shows that the boiler stays on On or Off more time then Cycle length AUTO ...

Page 7: ...ting season M_Set xx Purge aa a ps FR yy y ttsec LFR zz z Same as for the AUTO mode of operation see Purge description above PPrg aa a ps LFR yy y ttsec LFR zz z aa b ps FR 0 0 See PPrg on the OFF operation description Cyc A B ON E or Cyc A B OFF H Regular Cycle Same as for the AUTO mode of operation Manual OFF PPrg aa a ps LFR yy y ttsec LFR zz z aa b ps FR 0 0 see Post Purge description above Ma...

Page 8: ......

Page 9: ...nutes Pressure and Firing Rate 4 2ps FR 17 8 The pressure is represented in psi The Firing Rate FR is percent of the Gas Valve opening Compensator Compensator 1 Indicates the COMPENSATOR setting Time and Date 10 25am Sep10 08 Current time and date The am pm displayed with capital letters when Daylight Saving Time is in effect Outdoor Temperature OD Temp 52 F Temperature at the RTD outdoor sensor f...

Page 10: ... period as defined by the COLD NIGHT and NIGHT SETBACK settings Note If Out Door Temperature has been reached Day Mild or Cold Night Set Point the Boiler will be shut down via special procedure named Post Purge which is will be indicated on the right corner of the upper line of the LCD as PPrg operational state D Mild or N Mild operational state will be displayed for DAY NIGHT mild weather after P...

Page 11: ...Park Dr N Port Washington Phone 516 656 72211 Fax 516 626 7201 11 Fig 4 Heat Request vs Outdoor Temperature curves Mild Weather 55 Compensator 0 Fig 5 Heat Request vs Outdoor Temperature curves Mild Weather 55 Heat Gain 3 0 Compensator Sensitivity 3 0 ...

Page 12: ...s higher than this set point Range 40 to 80 F with 1 step Default value is 55 F N Mild NIGHT MILD WEATHER If the outdoor temperature is lower than this setpoint and the time is between 10PM and 5AM then the heat request value is corrected in accordance with the NIGHT SETBACK setting If the outdoor temperature is higher than this setpoint and the time is between 10PM and 5AM then the heat request i...

Page 13: ...culated ON period if ON bigger than Hit Limit Default value is 100 Motor Type Motorized valve nominal timing in seconds for 90 or 160 stroke Range 15 30 45 60 72 90 144 180 240 seconds Default 30seconds HeatUpStp New cycle will comment when the system temperature on the Cold Pipe Temperature Sensor reaches this set point please see diagram on Figures 5 7 red line Range 40 to 240 F Step 1 F Default...

Page 14: ...react on the High Pressure AUTO MAN SET and MAN ON In the AUTO and MAN SET mode of operations the controller will finish current operational Cycle and will not start the next until PRESSURE 2 PRESSURE_SP 0 2 psi hysteresis In the MAN ON mode the controller will close the fuel valve to 0 If the boiler was turned OFF before changing the operational mode to MAN ON it wouldn t turn the boiler ON until...

Page 15: ...Down key to make desired value then press Enter Set Pressure Sensor Value for maximum current 20ma 1 From Calibration Menu Select SetPSensor 20ma and press Enter 2 The upper line of the display indicates mode of operation CAL 3 The lower line of the display shows possible adjustment for example NewPSns 4ma 15psi 4 Press Up or Down key to make desired value then press Enter Pressure Sensor Calibrat...

Reviews: