3.5.4 Horn Function
The alarm relay is defined as horn relay by this parameter with the following possibilities to reset.
By pressing any of the 4 push-buttons (only possible in the starting menu).
Automatic reset at the end of the fixed time.
By an external push-button (assignment of the digital input).
The horn function is only activated if at least one of the two parameters (time or digital input) is set.
Special function Response
After acknowledging the relay (by push-button or externally) time starts. When this time has run out and the alarm
is still acting, the relay is set again.
Symbol Description Setting
Status
Function
R 04
Relay No.
Selection of relay
Quitt Mode
0
0 = Reset of
the relay after time having run out, or by push-button
1 = Reset of the relay by push-button, after time having run out and
when alarm is still acting, relay is set again. (Response function).
Time
120
Time for automatic reset function or response function
0 = no reset function
DI
0
Assignment, which digital input resets the relay.
Acknowledge the horn relay
Alarm 4
Relay 4
Gas concentration higher lower than threshold
Acknowledging
signal
On
Of
On
Off
On
Off
Time
Special function “Response”. (Return of the horn relay)
Alarm 4
Relay 4
Gas concentration higher lower than threshold
Acknowledging-
signal
On
Off
On
Off
On
Off
Time
Time
Specifications subject to change without notice. | USA 130917 | Page 12 of 22
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN
TEC
| relevantsolutions.com/inteccontrols
DGC3 – UserManual
Polygard® is a registered trademark of MSR | DGC3
Specifications subject to change without notice. | USA 160104 | Page 12 of 22
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN
TEC
| relevantsolutions.com/inteccontrols
DGC3 – UserManual
PolyGard
®
is a registered trademark of MSR-Electronic GmbH | DGC3
INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com
Specifications subject to change without notice. | USA 200211 | Page 12 of 22
DGC3 – UserManual