10  Notes and General Information

It is important to read this user manual thoroughly and clearly in order to understand the information 

and instructions. The PolyGard

®

 transmitter must be used within product specification capabilities. The 

appropriate operating and maintenance instructions and recommendations must be followed. Due to on-

going product development, IN

TEC 

and MSR reserves the right to change specifications without notice.

The information contained herein is based upon data considered accurate. However, no guarantee is 

expressed or implied regarding the accuracy of this data.

10.1  Intended Product Application

The PolyGard

®

 transmitter is designed and manufactured for control applications and air quality compliance 

in commercial buildings and manufacturing plants (i.e. detection and automatic exhaust fan control for 

automotive maintenance facilities, enclosed parking garages, engine repair shops, warehouses with 

forklifts, fire stations, tunnels, etc.).

10.2  Installers’ Responsibilities

It is the installer’s responsibility to ensure that all PolyGard

®

 transmitter is installed in compliance with all 

national and local codes and OSHA requirements. Installation should be implemented only by technicians 

familiar with proper installation techniques and with codes, standards and proper safety procedures for 

control installations and the latest edition of the National Electrical Code (ANSI/NFPA70). It is also essential 

to follow strictly all instructions as provided in the user manual.

10.3  Maintenance

It is recommended to check the PolyGard

®

 transmitter regularly. Due to regular maintenance, any 

performance deviations may easily be corrected. Re-calibration and part replacement in the field may be 

implemented by a qualified technician and with the appropriate tools. Alternatively, the easily removable 

plug-in transmitter card with the sensor may be returned for service to IN

TEC

 Controls.

10.4  Limited Warranty

MSR-Electronic-GmbH  and IN

TEC

 Controls warrants the PolyGard

®

 transmitter for a period of two 

years, 12 months normal exposure for the sensor, from the date of shipment against defects in material 

or workmanship. Should any evidence of defects in material or workmanship occur during the warranty 

period, IN

TEC

 Controls will repair or replace the product at their own discretion, without charge.

This warranty does not apply to units that have been altered, had attempted repair, or been subject to 

abuse, accidental or otherwise. The warranty also does not apply to units in which the sensor element 

has been overexposed or gas poisoned. The above warranty is in lieu of all other express warranties, 

obligations or liabilities.
This warranty applies only to the PolyGard

®

 transmitter. IN

TEC

 Controls or MSR shall not be liable for 

any incidental or consequential damages arising out of or related to the use of the PolyGard

®

 transmitter.

If the PolyGard® transmitter needs to be returned to IN

TEC

 Controls for service, an RMA number must be 

obtained prior to sending.

Specifications subject to change without notice. | USA 151203 | Page 14 of 14

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

AT-3300_V3 – UserManual

Polygard® is a registered trademark of MSR | AT-3300_V3_UserManual

Summary of Contents for PolyGard AT-3300 V3

Page 1: ...inted in USA 150313 March 13 2015 Revision Polygard is a registered trademark of MSR AT 3300_V3_UserManual PolyGard AT 3300 V3 Transmitter for Combustible Gases Serial No ET03 002 User Manual April 20...

Page 2: ...y data AT 34XX V3 7 5 3 Option Relay Output 8 6 Inspection and Service 9 6 1 Inspections 9 6 2 Calibration 9 6 3 Exchange of Sensor Element 9 7 Troubleshooting 9 7 1 Analog Mode 9 8 Technical Data 10...

Page 3: ...s voltage signal 0 2 10 V 2 2 Sensor The integrated sensor works according to the catalytic bead principle The ambient air being monitored diffuses through a sintered metal disk into the sensor Here t...

Page 4: ...rs with a density air the transmitter must be located at the highest point possible Gas density and mounting height can be read from the table Cross sensitivity data Choose mounting location of the se...

Page 5: ...for proper mounting at X4 and X5 Check the sensor for proper mounting at the connectors X8 of the PCB AT 33XX V3 only AT 34XX V3 Calibrate the transmitter if not already factory calibrated Required in...

Page 6: ...sor for correct mounting 5 1 2 Gain Connect calibration adapter carefully to the sensor element Apply calibration test gas 150 ml min 1 Bar 14 5 psi 10 Wait two minutes until the signal is stable adju...

Page 7: ...Benzene C6H6 44 1 30 2 70 Floor Cyclohexane C6H12 44 1 30 2 91 Floor Ethylene CH2 81 2 30 0 98 Ceiling Ethane C2H6 82 3 00 1 05 Floor Ethyl Alcohol C2H5OH 75 3 30 1 59 Floor Ethyl Acetate CH3COOC2H5 4...

Page 8: ...3 Relay 1 is equipped with a change over contact Via the MODBus interface the two alarm thresholds and the hysteresis are freely adjustable at the PC within the measuring range The procedure can be re...

Page 9: ...the sensor element into the PCB ET03 at XB7 XB8 Replug the PCB AT 33XX V3 into terminal blocks X4 X5 carefully Calibrate according to section 5 7 Troubleshooting 7 1 Analog Mode Trouble Cause Solution...

Page 10: ...e polarity protected Power consumption without options 35 mA max 0 85 VA Output signal Analog output signal Selectable Current tension Starting point 0 20 0 4 20 mA load 500 0 2 10 V load 50 k proport...

Page 11: ...ng Temperature controlled 3 C 2 C 37 5 F 3 6 F Ambient temperature 30 C 22 F Power supply 18 28 VDC AC Power consumption 0 3 A 7 5 VA Indications only for option stainless steel for further types see...

Page 12: ...NO NC XA3 1 XA3 2 Gain ET03_001 0 20 Test Bridge Connector Service Tool R1 X5 Zero Option Relay Anal Output V DC mA Anal Output Start Point 20 0 Function Relay R2 NO NC NC NO Option Manual Calibratio...

Page 13: ...B AT Specifications subject to change without notice USA 151203 Page 13 of 14 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 888 GO INTEC relevantsolutions com inteccontrols AT 3300_V3 Use...

Page 14: ...ance It is recommended to check the PolyGard transmitter regularly Due to regular maintenance any performance deviations may easily be corrected Re calibration and part replacement in the field may be...

Reviews: