8   Technical Data 

General sensor performances 

 

Gas type 

Combustible gases/ vapours 

See Ordering Information 

Sensor element 

Ex sensor, catalytic bead 

Pressure range 

Atmosphere ± 20 % 

Storage temperature range  

5 °C to 30 °C  (41 °F to 86 °F) 

Storage time 

Max. 6 months 

Mounting height 

Depending on gas type 

AT-33XX V3 

Measuring range  

0 - 100 % LEL  

Detection limit 

0,5 % LEL 

Accuracy 

± 1 % of signal/methane 

Repeatability 

± 2 % of signal/methane 

Long-term zero drift 

< 5 % measuring range/year 

Long-term sensitivity drift 

< 2 % measuring range/month 

Response time 

t

90

 < 10 sec./methane 

Life expectancy 

> 3 years/normal operating environment 

Temperature range 

- 10 °C to + 40 °C  (14 °F to 104 °F) 

Humidity, continuous 

15 – 90 % RH non condensing 

Humidity, intermitted 

0 – 99 % RH non condensing 

Electrical 

 

Power supply 

16 - 28 VDC/AC, reverse polarity protected 

Power consumption (without options) 

35 mA, max. (0,85 VA) 

Output signal 

 

Analog output signal 

Selectable: Current / tension 

                   Starting point 0 / 20 %  

(0) 4 – 20 mA, load 

 500 

(0) 2 - 10 V; load ≥ 50 k 

 

proportional, overload and short-circuit proof 

Serial interface 

 

Transceiver 

RS 485  / 19200 Baud 

Protocol, depending on version 

MSR_DT05 or MOD_Bus 

Physical

 

 

Enclosure* 

Stainless steel V2A 

Enclosure colour* 

Natural, brushed 

Dimensions* (H x W x D) 

113 x 135 x 45 mm /(5.35 x 4.5 x 1.8 in.) 

Weight* 

Approx. 0,5 kg (1.1 Ibs.) 

Protection class*

IP 55  

Mounting* 

Wall mounting, pillar mounting 

Cable entry 

Standard 1 x M 20 

Wire connection 

Screw-type terminal min. 0,25, to. 2,5 mm

2  

24 to 14 AWG 

Wire distance 

Current signal ca. 500 m (1500 ft.) 

Voltage signal ca. 200 m (500 ft.) 

Specifications subject to change without notice. | USA 151203 | Page 10 of 14

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

AT-3300_V3 – UserManual

Polygard® is a registered trademark of MSR | AT-3300_V3_UserManual

Summary of Contents for PolyGard AT-3300 V3

Page 1: ...inted in USA 150313 March 13 2015 Revision Polygard is a registered trademark of MSR AT 3300_V3_UserManual PolyGard AT 3300 V3 Transmitter for Combustible Gases Serial No ET03 002 User Manual April 20...

Page 2: ...y data AT 34XX V3 7 5 3 Option Relay Output 8 6 Inspection and Service 9 6 1 Inspections 9 6 2 Calibration 9 6 3 Exchange of Sensor Element 9 7 Troubleshooting 9 7 1 Analog Mode 9 8 Technical Data 10...

Page 3: ...s voltage signal 0 2 10 V 2 2 Sensor The integrated sensor works according to the catalytic bead principle The ambient air being monitored diffuses through a sintered metal disk into the sensor Here t...

Page 4: ...rs with a density air the transmitter must be located at the highest point possible Gas density and mounting height can be read from the table Cross sensitivity data Choose mounting location of the se...

Page 5: ...for proper mounting at X4 and X5 Check the sensor for proper mounting at the connectors X8 of the PCB AT 33XX V3 only AT 34XX V3 Calibrate the transmitter if not already factory calibrated Required in...

Page 6: ...sor for correct mounting 5 1 2 Gain Connect calibration adapter carefully to the sensor element Apply calibration test gas 150 ml min 1 Bar 14 5 psi 10 Wait two minutes until the signal is stable adju...

Page 7: ...Benzene C6H6 44 1 30 2 70 Floor Cyclohexane C6H12 44 1 30 2 91 Floor Ethylene CH2 81 2 30 0 98 Ceiling Ethane C2H6 82 3 00 1 05 Floor Ethyl Alcohol C2H5OH 75 3 30 1 59 Floor Ethyl Acetate CH3COOC2H5 4...

Page 8: ...3 Relay 1 is equipped with a change over contact Via the MODBus interface the two alarm thresholds and the hysteresis are freely adjustable at the PC within the measuring range The procedure can be re...

Page 9: ...the sensor element into the PCB ET03 at XB7 XB8 Replug the PCB AT 33XX V3 into terminal blocks X4 X5 carefully Calibrate according to section 5 7 Troubleshooting 7 1 Analog Mode Trouble Cause Solution...

Page 10: ...e polarity protected Power consumption without options 35 mA max 0 85 VA Output signal Analog output signal Selectable Current tension Starting point 0 20 0 4 20 mA load 500 0 2 10 V load 50 k proport...

Page 11: ...ng Temperature controlled 3 C 2 C 37 5 F 3 6 F Ambient temperature 30 C 22 F Power supply 18 28 VDC AC Power consumption 0 3 A 7 5 VA Indications only for option stainless steel for further types see...

Page 12: ...NO NC XA3 1 XA3 2 Gain ET03_001 0 20 Test Bridge Connector Service Tool R1 X5 Zero Option Relay Anal Output V DC mA Anal Output Start Point 20 0 Function Relay R2 NO NC NC NO Option Manual Calibratio...

Page 13: ...B AT Specifications subject to change without notice USA 151203 Page 13 of 14 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 888 GO INTEC relevantsolutions com inteccontrols AT 3300_V3 Use...

Page 14: ...ance It is recommended to check the PolyGard transmitter regularly Due to regular maintenance any performance deviations may easily be corrected Re calibration and part replacement in the field may be...

Reviews: