Avoid any force (e.g. by thumb) on the sensor element during operation or installation. Electronics can be
destroyedbystaticelectricity.Therefore,donottouchtheequipmentwithoutawriststrapconnectedtogroundor
withoutstandingonaconductivefloor.
Whenchoosingthemountingsitepleasepayattentiontothefollowing:
•
Thespecificweightofcarbonmonoxideisasmallerthanthatofair(factor0.97).
Recommendedmountingheightis1.5m(5feet)to1.8m(6feet)abovefloor.
•
Choosemountinglocationofthesensoraccordingtothelocalregulations.
•
Considertheventilationconditions!Donotmountthetransmitterinthecenteroftheairflow(airpassages,
suctionholes).
•
Mountthetransmitteratalocationwithminimumvibrationandminimumvariationintemperature(avoid
directsunlight).
•
Avoidlocationswherewater,oiletc.mayinfluenceproperoperationandwheremechanicaldamagemight
bepossible.
•
Provideadequatespacearoundthesensorformaintenanceandcalibrationwork.
Ductmounting
•
Mountonlyinastraightsectionofductwithminimumairvortex.Keepaminimumdistanceof1m(3,5feet)
fromanycurveorobstacle.
•
Mountonlyinaductsystemwithamaximumairvelocityof10m/s(2000ft/min)orless.
•
Mountingmustbeperformedsothattheprobeopeningsareinlinewiththeairflow.
•
Openthecover.UnplugbasicPCBcarefullyfromthebottompart.
•
Fixbottompartbyscrewsverticallytothewall(terminalblockstotheground).
•
PluginthebasicPCBatX4andX5withcare.Replacethecover.
Considerstaticelectricity!See3.Mounting
•
Installation of the electrical wiring should only be performed by a trained specialist according to the
connection diagram, without any power applied to conductors and according to the corresponding
regulations!
•
Avoidanyinfluenceofexternalinterferencebyusingshieldedcablesforthesignalline,butdonotconnect
theshield.
•
Recommended cable for analog mode: Belden Twisted Shielded (20 AWG), max. res. 73
/km (20.8
/1000ft).
•
ItisimportanttoensurethatthewireshieldsoranybarewiresdonotshortthemountedPCB.
Specifications subject to change without notice. | USA 141114 | Page 4 of 17
Polygard® is a registered trademark of MSR | AT-1110V3
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN
TEC
| relevantsolutions.com/inteccontrols
AT-1110_V3 – UserManual
Specifications subject to change without notice. | USA 160104 | Page 4 of 17
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN
TEC
| relevantsolutions.com/inteccontrols
AT-1110 V3 – UserManual
PolyGard
®
is a registered trademark of MSR-Electronic GmbH | AT-1110V3