PolyGard
®
CO Transmitter
User Manual - AT-1110 V3
Page 10
Jumper020%notset
Checkjumperposition
Powervoltagenotapplied
MeasuretensionatX4:
Twowire:Pin1(+)and4()
Threewire:Pin1(+)and2()
PCBAT1110notpluggedincorrectlyat
X4andX5
ReplugPCBcorrectly
Outputsignal<3mA/1.5V
and/orcontrolvoltage<30mV
onlyforstartingsignal2V/4mA
Wirebreak
Checkthewiring
Outputsignal>22mA/220mV Shortcircuit
Checkthewiring
Sensorelementnotcalibrated
Calibratesensorelement
Controlvoltagedoesnotreach
thecalculatedvalue
Sensorsensitivity<30%
Replacesensorelement
Powervoltagenotapplied
MeasuretensionatX4
Noreactionoftheoutputsignal
inspiteofgasconcentration
Signal(Pin4)notwiredcorrectly
Checkthewiring
ThecrosssensitivitydependsontheusedtransmittertypeandcanbereadfromthetableTechnicalData(see9.).
Othergasescanhaveaninfluenceonthesensitivity,too.Thetabledoesnotclaimtobecomplete.Theindicated
sensitivitydataareonlystandardvaluesreferringtonewsensorelements.
Specifications subject to change without notice. | USA 141114 | Page 10 of 17
Polygard® is a registered trademark of MSR | AT-1110V3
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN
TEC
| relevantsolutions.com/inteccontrols
AT-1110_V3 – UserManual
Specifications subject to change without notice. | USA 160104 | Page 10 of 17
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN
TEC
| relevantsolutions.com/inteccontrols
AT-1110 V3 – UserManual
PolyGard
®
is a registered trademark of MSR-Electronic GmbH | AT-1110V3