3.12.2. Silent alarm and alarm time delay
Notes:
•
The silent alarm function and the corresponding output signal are only active
when the function has been activated.
•
The silent alarm is triggered by entering the opening code, whereby the last
digit has to be increased by one.
Example:
0 123456
Normal opening code
0 123457 Triggering of the silent alarm (9+1 -> 0)
•
After a silent alarm has been triggered, a programmed alarm time delay
becomes active. The release time of the alarm time delay is permanently set
to 5 minutes.
•
The alarm signal can either be signaled and connected via the
EloXT
expansion unit
(relay output) or via the adapter p.c.b.
EloAdapt
(open
collector output).
•
The triggering of a silent alarm is also saved in the event log.
•
The silent alarm and alarm time delay functions can also be programmed with
the PC software CombiComm.
Activation of the “silent alarm”
*9*
Enter program number 9
123456 *
1
Enter the
master code
02*
Enter the user
function number
(e.g. 02)
01*
1
Enter the opening delay in the case of an alarm
in minutes, e.g. 01 minute.