SRC - C1    

 

Page 3 

Subject to alteration 

Mounting location

 

Mount the transmitter on a flat interior wall of the room to be controlled. Do avoid obstructions such as shelves, 

curtains and recesses. Do not place near heat sources, draft channels. Do not expose to direct sunlight.  

Installation

 

1.

 

Open the single screw on the cover and remove cover from mounting plate. 

2.

 

Fix the mounting plate to the flush mounting box or the wall surface 

3.

 

Connect the conductors to the terminals of the back part according to wiring diagram 

4.

 

The end of the conduit at the sensor must be sealed to prevent false measurements due to draughts through 

the conduit.  

5.

 

Slide the two hooks on top of the cover into the two latches on top of the mounting plate.  

6.

 

Close the cover.  

7.

 

With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure the cover to the 

back part. There is no need to tighten the screw too much. 

Connection terminals

 

 

1: G 

Power supply 24VAC, +24VDC 

2: G0  Power supply 0VAC, -24VDC 

3: U1  JP1 = 1-2, voltage output of CO2 transmitter 0…10V or 2…10V (JP2) 

3: I1 

JP1 = 2-3, current output of CO2 transmitter 0…20mA or 4…20mA (JP2) 

J umper Settings

 

 

JP1 Signal type 

JP2 Signal range 

U1:  

0-10V 

I1:  

0-20mA 

 

U1:  

2-10V 

I1:  

4-20mA 

 

 

 
 

U1 

0-10V, 2-10V 

 

I1 

0-20mA, 4-20mA 

 

 

 
 

Status LED 

LED indicates status 

No light: no power or unit damaged 

5 sec blinking: Normal  

2 sec blinking: OPA-S connected 

1 sec blinking: Sensor element error 

if alternate in 2 sec interval with air 

quality LED: Calibration is active. 

OPA-S 

1  2  3 

JP1 

 

 

JP2 

 

 

STATUS 

JP3

 

 

 

 

1  2  3  4 

Calib:    0    400 ppm 

G

 

24

G

0V

 

U

1/

 I1

 

AO

 C

O2

  

JP3 Calibration 

Calibrate 0 ppm 

Provide CO2 free gas 

 

Calibrate 400 ppm 

Provide clean fresh air 

 

Standard position, 

 

No calibration

 

 

 

 

 

1  2  3  4 

 

 

 

1  2  3  4 

 

 

 

1  2  3  4 

Air Quality 

Air Quality LED 

LED indicates status 

No light : no power or unit damaged  

Green   : Low CO2 level  

Orange  : Medium CO2 level 

Red 

: High CO2 level 

Green blinking: 0ppm calibration 

Red blinking: 400ppm calibration 

Note:

 JP3 must be either removed or placed 

at position 2-3 anytime when not calibrating! 

   0VAC 

-24VDC 

 24V ADC 

SRC - C1  

G0 

U1/I1 

CO2 out  

 

Output signal configuration

 

The analog output signal type may 

be configured with a jumper for 0-

10 VDC or 0-20 mA control 

signals. The jumpers are located 

next to the terminal connector of 

each analog output. See table 

below for jumper placement. The 

factory setting is to 0-10 VDC. 

 

The signal range may be set with 

JP2 for both analog outputs. JP2 

will only operate if the output 

range specified with OP01 and 

OP02 is left at the default position 

of 0…100%. With any other 

setting the position of JP2 has no 

influence and the range defined 

with the output parameters 

applies. 

Insight  Control

Ph 1300 665 831

www.insightcontrol.net.au

Summary of Contents for SRC-C1

Page 1: ... Indication of air quality A three color LED is used to indicate air quality Green light for low CO2 concentration orange light for medium and red light for high concentration The levels for low medium high may be programmed Default settings are 0 ppm low 800 ppm medium 1500 ppm high Use as P controller Set a minimum concentration when the extract fan should start to run at its minimum speed For e...

Page 2: ...ion Climatic Conditions Temperature Humidity To IEC 721 3 3 class 3 K5 0 50 C 32 122 F 95 R H non condensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 30 70 C 22 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive Low Voltage Directive 2004 108 EC 2006 95 EC Product standards Automa...

Page 3: ...4 20mA 3 2 1 3 2 1 Status LED LED indicates status No light no power or unit damaged 5 sec blinking Normal 2 sec blinking OPA S connected 1 sec blinking Sensor element error if alternate in 2 sec interval with air quality LED Calibration is active OPA S 1 2 3 JP1 JP2 STATUS JP3 1 2 3 4 Calib 0 400 ppm G 24V G0 0V U1 I1 AO CO2 JP3 Calibration Calibrate 0 ppm Provide CO2 free gas Calibrate 400 ppm P...

Page 4: ...tuning speed is however limited to about 30 ppm week For post calibration convenience in the event that one cannot wait for the ABC algorithm to cure any calibration offset jumper 3 is provided for the operator to choose calibration options If jumper 3 is placed on position 1 2 for a minimum time of 8 seconds the internal zero calibration is executed in which case the sensor must be purged by some...

Reviews: