5 Parameter Table
- 40 -
■
Group F6: Start/Stop Control
Para. No.
Para. Name
Setting Range
Unit
Default
Commission
F6-00
Start mode
0: Direct startup
1: Reserved
2: Pre-excited startup
(asynchronous motor)
N.A.
0
F6-01
Mode of catching a
spinning motor
0: From stop frequency
1: From zero speed
2: From max. frequency
N.A.
0
F6-02
Speed of catching a
spinning motor
1 to 100
N.A.
20
F6-03
Startup frequency
0.00 to 10.00
Hz
0.00
F6-04
Startup frequency active
time
0.0 to 100.0
s
0.0
F6-05
DC injection braking 1
level/Pre-excitation level
0 to 100
%
50
F6-06
DC injection braking 1
active time/Pre-excitation
active time
0.0 to 100.0
s
0.0
F6-07
Acceleration/ Deceleration
mode
0: Linear mode
1: S-curve mode A
2: S-curve mode B
N.A.
0
F6-08
Time proportion of S-curve
start segment
0.0 to (100.0 minus F6-09) %
30.0
F6-09
Time proportion of S-curve
end segment
0.0 to (100.0 minus F6-08) %
30.0
F6-10
Stop mode
0: Decelerate to stop
1: Coast to stop
N.A.
0
F6-11
DC injection braking 2
frequency threshold
0.00 to 10.00
Hz
0.00
F6-12
DC injection braking 2
delay time
0.0 to 100.0
s
0.0
F6-13
DC injection braking 2 level 0 to 100
%
50
F6-14
DC injection braking 2
active time
0.0 to 100.0
s
0.0
F6-15
Reserved
-
-
-
F6-18
Catching a spinning motor
current limit
30 to 200
%
Model
dependent
F6-21
Demagnetization time
0.00 to 5.00
s
Model
dependent
F6-22
Min. output frequency
0.00 to F6-11
Hz
0.00
F6-23
Factory reserved
1 to 100
N.A.
10