Version 1.0 09/08/2017
http://www.inorea.com
29
No.
Code
Parameter name
Functional Description
Smallest unit Change
Reference page
14.
d0.14
PID feedback value
Feedback value percentage
under PID adjustment mode
1%
●
47
15.
d0.15
Current stage of multi-
speed
Current stage of multi-speed
-
●
47
16.
d0.16
Reserved
17.
d0.17
Inverter module
temperature
0 to 100.0
℃
0.1
℃
●
47
18.
d0.18
Software version
DSP software version number
-
●
47
19.
d0.19
Cumulative running
time of this unit
0 to 65535h
1h
●
47
20.
d0.20
Torque setting value
Observe the set command torque
under speed mode or torque
control mode
0.1%
●
47
5-1-2.F0 Group - Basic function
No.
Code
Parameter name
Setting range
Factory default Change
Reference page
21.
F0.00
Control mode
0: Open-loop flux vector
control
1: Reserved
2: V/F control
3: torque control
2
★
47
22.
F0.01
Keyboard set
frequency
0.00Hz to F0.08 (maximum
output frequency)
50.00Hz
☆
48
23.
F0.02
Frequency
command
selection
0: keyboard setting
1: Analog AI1 setting
2: Analog AI2 setting
3: Panel potentiometer setting
4: AI1+ AI2 setting
5: Multi-speed operation setting
6: PID control setting
7: Remote communications setting
0
★
48
24.
F0.03
Keyboard and terminal
UP/DOWN setting
0: Valid, and the inverter power
failure with data storage
1: Valid, and the inverter power
failure without data storage
2: UP/DOWN setting is invalid
3: Valid when running, invalid
when stop
0
☆
49
25.
F0.04
Command source
channel
0: Keyboard command channel
1: Terminal command channel
2: Communication command
channel
0
★
50