i

DELAY 1

0

 to

500 Sec.

This parameter will be prompted only if selected control action is ON-OFF. 
It sets the main output restart time where O/P once turned off will turn ON 
only after restart time, regardless difference between PV & SP in Heat or 
Cool mode. If set to '0', O/P will be switched without delay. Also, Delay will 
be applicable in case of every power ON.

90 Sec.

CONTROL

HYS

o

1 to 25  C

This parameter will be prompted only if selected control action is ON-OFF. 
It sets the dead band between ON & OFF switching of the Output. Larger 
value of hysterisis minimize the number of ON-OFF operation to the load. 
This  increases  life  of  actuators  like  contactors  but,  also  produces  large 
errors (between PV & SV).

2°C

OUTPUT

OFF

1  to 10 

This parameter will be prompted only if selected control action is PID. 
With this parameter  O/P will be Completely OFF after the Set Point + 
Offset Value. If Disable, O/P will act Depending upon the PID Value after 
Set Point achieved.

Disable

User can set ramp rate/min for SP1 (Set Point) to minimize overshoot. 

This parameter will be available only if Enabled in Configuration List. 

RAMP

RATE

o

 0.0  C

to

o

 25.0  C

User  can  change  SP  value  using  UP/  DOWN  keys.  Holding  the  key,   will 
change  the  value  at  a  faster  rate.  Press  SET  key  to  store  the  desired 
value & move on to the next parameter. 

o

0 C

Disable

LSPL ~ HSPL 

CONTROL

SET

POINT

PROGRAMMING

USER LIST :

 To access the user list press SET key once.

LOWER

DISPLAY

UPPER

DISPLAY

 PARA

METER

RANGE

DESCRIPTION

DEFAULT

LOWER

DISPLAY

UPPER

DISPLAY

 PARA

METER

RANGE

DESCRIPTION

DEFAULT

PROPORTIONAL

BAND

0.5 

to 

99.9°C

This  parameter  will  be  prompted  only  if  selected  control  action  is  PID.  It 
sets  bandwidth  over  which  the  output  power  is  adjusted  depending  upon 
the error (SV-PV). The value of this parameter is automatically set by Auto 
tune function.

o

5.0 C

INTEGRAL

TIME

to 

9999 Sec.

This  parameter  will  be  prompted  only  if  selected  control  action  is  PID.  It 
sets  the  time  taken  by  PID  algorithm  to  remove  steady  state  error.  The 
value of this parameter is automatically set by Auto tune function. If set to 
‘0’, this function will be disabled.

240

DERIVATIVE

TIME

to 

300 Sec.

This  parameter  will  be  prompted  only  if  selected  control  action  is  PID.  It 
defines  how  strongly  the  controller  will  react  to  the  rate  of  change  of  PV. 
The  value  of  this  parameter  is  automatically  set  by Auto  tune  function.  If 
set to ‘0’, this function will be disabled.

60

CYCLE

TIME

0.5

 to 

100.0 Sec.

This  parameter  will  be  prompted  only  if  selected  control  action  is  PID. 
User  can  set  this  value  based  on  process  being  controlled  &  type  of 
output  being  selected.  For  Relay  O/P,  cycle  time  should  be  more  than 
12sec & for SSR O/P, cycle time should  be less than 10sec.

16.0 Sec.

0

Set this parameter to 15 (Default LOCK CODE) to access Control List.
User has a choice to set different Lock Code via USER LOCK CODE in 
Config. List.

1 ~ 9999

LOCK
CODE

CONTROL LIST :

 To enter in this mode, press SET & DOWN key simultaneously for 3 sec. User can then set 

the control parameters.

100 %

OUTPUT
 POWER

LIMIT

0.0 %

TO

100.0 %

This  parameter  will  be  prompted  only  if  selected  control  action  is  PID. 
This parameter will decide the Max. output power in % applied to the load.

3

OIM Px-X18

e

 V2.1 Page 3 of 5

0

User has a choice to set different Lock Code via USER LOCK CODE in Config. List.

Set this parameter to 15 (Default LOCK CODE) to access Config. List.

LOCK
CODE

LOWER

DISPLAY

UPPER

DISPLAY

 PARA

METER

DESCRIPTION

DEFAULT

CONFIGURATION LIST :

 (1) To enter in this mode, press and hold SET & UP key simultaneously for 3 sec.

(2) Press UP or DOWN key to scroll between parameter options.
(3) Press SET key to store the current parameter & move on to the next parameter.

TC - J

INPUT

TYPE

This parameter value is set according to the type of sensor (Thermocouple or RTD 
input) connected to the controller's input terminals. 

Fe-k(J) T/C

Cr-AL(K) T/C

Pt-100(RTD)

Pt-100(RTD 0.1)

Sensor Type 

Accuracy

o

760 C

o

-99 

1300 C

o

-100 

450 C

o

-20.0 

100.0 C

Resolution

Range

o

1  C

o

1  C

o

1  C

o

0.1  C

}

  

±

o

C

o

0.3  C

  

±