i
DELAY 1
0
to
500 Sec.
This parameter will be prompted only if selected control action is ON-OFF.
It sets the main output restart time where O/P once turned off will turn ON
only after restart time, regardless difference between PV & SP in Heat or
Cool mode. If set to '0', O/P will be switched without delay. Also, Delay will
be applicable in case of every power ON.
90 Sec.
CONTROL
HYS
o
1 to 25 C
This parameter will be prompted only if selected control action is ON-OFF.
It sets the dead band between ON & OFF switching of the Output. Larger
value of hysterisis minimize the number of ON-OFF operation to the load.
This increases life of actuators like contactors but, also produces large
errors (between PV & SV).
2°C
OUTPUT
OFF
1 to 10
This parameter will be prompted only if selected control action is PID.
With this parameter O/P will be Completely OFF after the Set Point +
Offset Value. If Disable, O/P will act Depending upon the PID Value after
Set Point achieved.
Disable
User can set ramp rate/min for SP1 (Set Point) to minimize overshoot.
This parameter will be available only if Enabled in Configuration List.
RAMP
RATE
o
0.0 C
to
o
25.0 C
User can change SP value using UP/ DOWN keys. Holding the key, will
change the value at a faster rate. Press SET key to store the desired
value & move on to the next parameter.
o
0 C
Disable
LSPL ~ HSPL
CONTROL
SET
POINT
PROGRAMMING
USER LIST :
To access the user list press SET key once.
LOWER
DISPLAY
UPPER
DISPLAY
PARA
METER
RANGE
DESCRIPTION
DEFAULT
LOWER
DISPLAY
UPPER
DISPLAY
PARA
METER
RANGE
DESCRIPTION
DEFAULT
PROPORTIONAL
BAND
0.5
to
99.9°C
This parameter will be prompted only if selected control action is PID. It
sets bandwidth over which the output power is adjusted depending upon
the error (SV-PV). The value of this parameter is automatically set by Auto
tune function.
o
5.0 C
INTEGRAL
TIME
0
to
9999 Sec.
This parameter will be prompted only if selected control action is PID. It
sets the time taken by PID algorithm to remove steady state error. The
value of this parameter is automatically set by Auto tune function. If set to
‘0’, this function will be disabled.
240
DERIVATIVE
TIME
0
to
300 Sec.
This parameter will be prompted only if selected control action is PID. It
defines how strongly the controller will react to the rate of change of PV.
The value of this parameter is automatically set by Auto tune function. If
set to ‘0’, this function will be disabled.
60
CYCLE
TIME
0.5
to
100.0 Sec.
This parameter will be prompted only if selected control action is PID.
User can set this value based on process being controlled & type of
output being selected. For Relay O/P, cycle time should be more than
12sec & for SSR O/P, cycle time should be less than 10sec.
16.0 Sec.
0
Set this parameter to 15 (Default LOCK CODE) to access Control List.
User has a choice to set different Lock Code via USER LOCK CODE in
Config. List.
1 ~ 9999
LOCK
CODE
CONTROL LIST :
To enter in this mode, press SET & DOWN key simultaneously for 3 sec. User can then set
the control parameters.
100 %
OUTPUT
POWER
LIMIT
0.0 %
TO
100.0 %
This parameter will be prompted only if selected control action is PID.
This parameter will decide the Max. output power in % applied to the load.
3
OIM Px-X18
e
V2.1 Page 3 of 5
0
User has a choice to set different Lock Code via USER LOCK CODE in Config. List.
Set this parameter to 15 (Default LOCK CODE) to access Config. List.
LOCK
CODE
LOWER
DISPLAY
UPPER
DISPLAY
PARA
METER
DESCRIPTION
DEFAULT
CONFIGURATION LIST :
(1) To enter in this mode, press and hold SET & UP key simultaneously for 3 sec.
(2) Press UP or DOWN key to scroll between parameter options.
(3) Press SET key to store the current parameter & move on to the next parameter.
TC - J
INPUT
TYPE
This parameter value is set according to the type of sensor (Thermocouple or RTD
input) connected to the controller's input terminals.
Fe-k(J) T/C
Cr-AL(K) T/C
Pt-100(RTD)
Pt-100(RTD 0.1)
Sensor Type
Accuracy
o
0
~
760 C
o
-99
~
1300 C
o
-100
~
450 C
o
-20.0
~
100.0 C
Resolution
Range
o
1 C
o
1 C
o
1 C
o
0.1 C
}
1
±
o
C
o
0.3 C
±