High performance 

No-Break

TM 

DC 

UPS system 

 

Separate outputs for load and battery 

 

Battery detection - regular battery presence and 
battery circuit integrity checks 

 

Deep discharge protection for batteries 

 

Battery condition test (BCT) standard for models 
with communication port option 

 

Overload, short circuit & reverse polarity protec-
tion for battery 

 

Automatic battery temperature compensation 

 

Optional serial communication interface allows 
remote monitoring & user control of BCT function - 

and V versions 

 

No transition switching between PSU & battery 

 

LED flash codes for precise state indication 

 

“Mains” & “Battery System” alarm relay outputs 

ENVIRONMENTAL

 

Operating   
temperature 

 

Storage temperature 

 

Humidity 

 

Cooling 
 

♦ 

24 Month Warranty 

Input Voltages 
▪ standard 
 
▪ optional 

 

 

 

Fusing / Protection 

 

Isolation 

 

Efficiency 

 

Inrush current

 

 

Output Power

 

 

Output Voltages

 

 

Voltage adj. range

 

 

Temp. Compensation

 

 

 

 

Current Limit  

 

Line Regulation

 

 

Load Regulation 

 

Noise 

 

Drift

 

 

Hold-up time

 

 

Thermal Protection 
 

 

Overvoltage protection 

 
 

EMI 
 
Safety

 

 
 

 
 

 

 

ELECTRICAL  

 
180V - 264V, 45-65Hz 

 

88V - 132VAC  (internal link select) 
88-135VDC (specify at time of order) 

 

Internal input fuse, output battery fuse 

 

1KV DC input - output / earth 

 

> 85% 

 

Soft start circuit 

 

250W continuous (0 - 50°C)  

 

13.8/ 27.6/ 34.5/ 41.4/ 55.2V 

 

85 - 105% of Vout 

 

Temperature sensor on 1.7m lead with adhe-
sive pad:  -4mV / °C / cell ±10% 

 

Straight line profile  

 

<0.2% over AC input range 

 

<0.4% open circuit to 100% load 

 

<1% 

 

0.03% / °C 

 

15 - 20 ms (nom. - max. Vin) without battery 

 

Automatic current de-rating if >50°C. Self-
resetting. 

 

Over-voltage protection on output  
at ~ 130% of nominal output voltage 

 

CISPR 22 / EN55022 class A 
 
IEC950 / EN60950 / AS/NZS3260 

0 - 50 °C ambient at full load 
De-rate linearly >50 °C to 0 load @ 70 °C 

 

-10 to 85 °C ambient 

 

0 - 95% relative humidity non-condensing 

 

Natural Convection except for 12V model 
(fan) 

No-Break

™ FUNCTIONS AND ALARMS*

 

Battery Charge  Limit 
 
 
Reverse Polarity 
 
 
Battery Monitoring 
 
 
 
Battery Protection 
 

battery discharged 

 

 
 
 

overload (*refer to 

options - ECB) 
 

 

- short circuit  

 
Indication LEDs 
 

 

Alarms  
 
 
 
 
 
Alarm Relay contacts 
 
 
Battery Condition Test 
(BCT) 
 
Standby Mode 
 

See Model Table for default settings -  
may be increased to PSU rated current 
 
Battery reverse connection will open internal 
fuse (and produce alarm) 
 
Detects for presence of battery on start up, 
then every 60 minutes when charge current < 
200mA 
 
Electronic Circuit Breaker (ECB) operates 
under the following conditions: 
ELVD (electronic low voltage disconnect) 
activates when battery voltage drops to 1.67V/
cell (adjustable) - auto reset 
 
Allows ~150% load from battery without act-
ing,  operates within 300ms for total load > 
600% 
Acts within 2ms, backed up by fuse 

 
Green: 

Battery System OK,  Power OK 

Red:   

Standby 

 

• 

Mains Fail (Mains or PSU fail, standby 
mode) 

• 

Battery System OK -  alarms when battery 
voltage low (on mains fail) , battery 
missing, battery circuit wiring faulty, BCT 
fail (if enabled) 

C - NO - NC full changeover rated 1A /50V 
DC, 32VAC 
 
Standard on 

SR250

i & V

 

- 20mins/28days 

unless otherwise specified on ordering. 
 
Turns off DC output of PSU & allows load to 
run off battery 

Optional 

+PROTOCONMB

 

RS485 converter for 
use with SR250

i -485 

versions 

250W PSU/Charger with communication options 

Global Solutions Personal Focus 

SPECIFICATIONS   

All specifications are typical at nominal input, full load and at 20°C unless otherwise stated. 

Summary of Contents for No-Break SR250i 485 Series

Page 1: ...1 www innovative co nz Phone 64 9 835 0700 Fax 64 9 837 3446 NZ Freephone 0800 654 668 AU Freephone 1800 148 494 Email info innovative co nz No BreakTM DC UPS with RS485 communications port 250W SR250...

Page 2: ...in the installation to minimise the risk of ingress of water or dust Water will almost always cause instant failure the effects of dust are slower in causing failure of electronic equipment All elect...

Page 3: ...AL OPERATION LOAD CURRENT PSU MAX CURRENT ELECTRONIC CIRCUIT BREAKER POWER CONVERSION BATTERY MANAGEMENT ALARM CIRCUIT BATTERY CURRENT SENSE OUTPUT VOLTAGE CURRENT LIMIT BATTERY CHARGE CURRENT CONTROL...

Page 4: ...IRCUIT POWER CONVERSION I I LOAD CURRENT 1 5 x PSU MAX CURRENT MAINS FAIL BATTERY LOW ELECTRONIC CIRCUIT BREAKER REVERSE POLARITY FUSE BATTERY BATTERY TEMP SENSOR LOAD LOAD BATTERY LOAD LOAD OUTPUT VO...

Page 5: ...ed battery from load Residual current drain on battery following ELVD 1 mA Alarm Normal System is in STANDBY mode due to 1 Operator pressed standby button or 2 PSU has internal fault Alarm Alarm PSU i...

Page 6: ...ing if 50 C Self resetting Over voltage protection on output at 130 of nominal output voltage CISPR 22 EN55022 class A IEC950 EN60950 AS NZS3260 0 50 C ambient at full load De rate linearly 50 C to 0...

Page 7: ...t Overload protection may be customized Please call us for further information DC Output Output V PSU Rated A Charge Limit A 1 Recomm Load A Peak load A SR250i 12 13 8 18 0 9 0 12 0 27 SR250i 24 27 6...

Page 8: ...ppear at the load terminals and the BATLOW alarm relay energises The MAINS FAIL LED stays on for about 30 seconds 7 Connect load wiring to LOAD and LOAD terminals 8 Turn on ac power 9 After the batter...

Page 9: ...measured as at step 3 above should be exactly the same on both the load and battery outputs FRONT PANEL LEDS WITH BUILT IN SWITCHES For full list of LED flash codes please refer to page 5 BATTERY SYST...

Page 10: ...t may not detect a missing battery for up to this time 60 min BCT length of battery condition test 20 min Ret retest option N after a failed BCT further scheduled BCTs are inhibited Y after a failed B...

Page 11: ...232 programming output Information on the power supply parameters and control of the battery condition test function are available using these outputs PROCEDURE Install Software from disk Power MBLink...

Page 12: ...to the one of the available ports listed and click Open Com Port If it is the correct one in the Notice section Type should go from Notice to Success In Converter Information Click on Get Specs The c...

Page 13: ...ture will be displayed as below In this screen you will also be able to control the battery condition test parameters under Battery Condition Test sec tion Go to Settings Diagnostics tab The power sup...

Page 14: ...Mains Failure Possible Mains PSU Fail Battery in Bad Condition Communications to PSU Fail eg on LV disconnect Overload System Down Battery Missing Battery Low Possible Battery Missing Alarm State Sign...

Page 15: ...42mm 253mm 80mm 162mm 150mm 80mm NOTE power cord protrudes The Standard ac approx 70mm 76 5 mm 60 mm 80mm 242mm 80mm 80mm 242mm 253mm 80mm 162mm 150mm 270mm 278mm NOTE power cord protrudes 172mm 80mm...

Page 16: ...gies Ltd warrants its power supplies for 24 months two years from date of shipment against material and workmanship defects Innovative Energies liability under this warranty is lim ited to the replace...

Reviews: