5
Please note that the last four conditions apply only if the battery condition test option is enabled.
Battery
System OK
LED
Power OK
LED
Power
Stand-by
LED
Power OK
Alarm
Battery
System
OK Alarm
Condition
Normal
Normal
System Normal
: AC power is on, PSU output is OK, battery circuit is OK and bat-
tery voltage is > V Battery Low.
Normal
Normal
Battery Detection test in progress / imminent
(LED begins flashing 10 sec. prior
to test of < 1 sec).
Normal
Alarm
System AC power is on, PSU output is OK but either:
1.
Internal battery fuse has opened (only if battery has been reverse polarity
connected),
or
2.
Battery circuit open - battery missing, or fuse / circuit breaker / wiring fault.
Alarm
Normal
Either AC power has failed,
or
PSU has failed.
Battery system is OK
Alarm
Alarm
AC Power is off / DC has failed
and
battery has discharged to < V Battery Low, unit
will continue delivering battery current until low level initiates ELVD.
Alarm
Alarm
AC Power is off / DC has failed
and
ELVD has activated and disconnected battery
from load. Residual current drain on battery following ELVD <1 mA.
Alarm
Normal
System is in STANDBY mode due to :
1.
Operator pressed standby button,
or
2.
PSU has internal fault
Alarm
Alarm
PSU is in standby
and
battery has discharged to < Battery Low, unit will continue
delivering battery current until next level initiates ELVD.
Alarm
Alarm
PSU is in standby
and
ELVD has activated and disconnected battery from load.
Residual current drain on battery following ELVD < 1mA
Normal
Normal
Battery Condition Test is in progress: LEDs flash alternately
Normal
Alarm
Battery Condition Unserviceable:
failed to maintain terminal voltage during bat-
tery condition test
Alarm
Alarm
PSU is in standby mode
and
battery condition is determined as unserviceable:
failed to maintain terminal voltage during battery condition test
LEGEND :
=Off
=Flashing
=On
=Flashing Slowly
Global Solutions Personal Focus
LED FLASH CODES
ELECTRONIC CIRCUIT BREAKER (ECB)
The ECB is activated under the following conditions:
1.
battery voltage drops below the Vdisco (1.66V/cell)
2.
battery overcurrent or overload (refer to page 3)
The ECB will latch open only when there is no mains input present. It will reset when mains power is restore or can be
manually reset by following the procedure in step 6 on page 8 of this manual.