background image

 

Specifications are subject to change without notice.   No liability accepted for errors or omissions. 

 

                            12 

In “Communications Setup”

Set the address to the one of the available ports listed and click Open Com Port.  If it is the correct one, in the “Notice” 
section  “Type” should go from “Notice” to “Success”. 

In “Converter Information”

Click on “Get Specs”.   The converter information will be displayed as below. 
(Note that sometimes you may have to click on “Get Specs” twice) 

Global Solutions Personal Focus 

Summary of Contents for No-Break SR250i 485 Series

Page 1: ...1 www innovative co nz Phone 64 9 835 0700 Fax 64 9 837 3446 NZ Freephone 0800 654 668 AU Freephone 1800 148 494 Email info innovative co nz No BreakTM DC UPS with RS485 communications port 250W SR250...

Page 2: ...in the installation to minimise the risk of ingress of water or dust Water will almost always cause instant failure the effects of dust are slower in causing failure of electronic equipment All elect...

Page 3: ...AL OPERATION LOAD CURRENT PSU MAX CURRENT ELECTRONIC CIRCUIT BREAKER POWER CONVERSION BATTERY MANAGEMENT ALARM CIRCUIT BATTERY CURRENT SENSE OUTPUT VOLTAGE CURRENT LIMIT BATTERY CHARGE CURRENT CONTROL...

Page 4: ...IRCUIT POWER CONVERSION I I LOAD CURRENT 1 5 x PSU MAX CURRENT MAINS FAIL BATTERY LOW ELECTRONIC CIRCUIT BREAKER REVERSE POLARITY FUSE BATTERY BATTERY TEMP SENSOR LOAD LOAD BATTERY LOAD LOAD OUTPUT VO...

Page 5: ...ed battery from load Residual current drain on battery following ELVD 1 mA Alarm Normal System is in STANDBY mode due to 1 Operator pressed standby button or 2 PSU has internal fault Alarm Alarm PSU i...

Page 6: ...ing if 50 C Self resetting Over voltage protection on output at 130 of nominal output voltage CISPR 22 EN55022 class A IEC950 EN60950 AS NZS3260 0 50 C ambient at full load De rate linearly 50 C to 0...

Page 7: ...t Overload protection may be customized Please call us for further information DC Output Output V PSU Rated A Charge Limit A 1 Recomm Load A Peak load A SR250i 12 13 8 18 0 9 0 12 0 27 SR250i 24 27 6...

Page 8: ...ppear at the load terminals and the BATLOW alarm relay energises The MAINS FAIL LED stays on for about 30 seconds 7 Connect load wiring to LOAD and LOAD terminals 8 Turn on ac power 9 After the batter...

Page 9: ...measured as at step 3 above should be exactly the same on both the load and battery outputs FRONT PANEL LEDS WITH BUILT IN SWITCHES For full list of LED flash codes please refer to page 5 BATTERY SYST...

Page 10: ...t may not detect a missing battery for up to this time 60 min BCT length of battery condition test 20 min Ret retest option N after a failed BCT further scheduled BCTs are inhibited Y after a failed B...

Page 11: ...232 programming output Information on the power supply parameters and control of the battery condition test function are available using these outputs PROCEDURE Install Software from disk Power MBLink...

Page 12: ...to the one of the available ports listed and click Open Com Port If it is the correct one in the Notice section Type should go from Notice to Success In Converter Information Click on Get Specs The c...

Page 13: ...ture will be displayed as below In this screen you will also be able to control the battery condition test parameters under Battery Condition Test sec tion Go to Settings Diagnostics tab The power sup...

Page 14: ...Mains Failure Possible Mains PSU Fail Battery in Bad Condition Communications to PSU Fail eg on LV disconnect Overload System Down Battery Missing Battery Low Possible Battery Missing Alarm State Sign...

Page 15: ...42mm 253mm 80mm 162mm 150mm 80mm NOTE power cord protrudes The Standard ac approx 70mm 76 5 mm 60 mm 80mm 242mm 80mm 80mm 242mm 253mm 80mm 162mm 150mm 270mm 278mm NOTE power cord protrudes 172mm 80mm...

Page 16: ...gies Ltd warrants its power supplies for 24 months two years from date of shipment against material and workmanship defects Innovative Energies liability under this warranty is lim ited to the replace...

Reviews: