Innovative Circuit Technology Ltd.
15
The
Sequence/Cycle Delay
time must be set on the
Device Setup
page with
duration long enough for the connected network hardware to fully reset for
this function to be effective. Multiple outputs that are disabled using Power
Cycling will be re-enabled in sequence.
Output Load Shedding:
Enable Load Shedding
: Check this box to disable this output when the
system voltage drops below the load-shedding threshold for at least 30s.
This feature can be used to disconnect less critical loads to preserve back-up
battery power as the battery voltage drops.
Load-Shedding Threshold
: Enter the voltage level at which the selected
output will be disconnected.
Load-Shedding Auto Recovery
: Check this box to allow the output to be
automatically reconnected when the system voltage is above the
Auto
Recovery Threshold
for at least 60s. The output must be manually re-
enabled using the
Output ON
button on the Status & Control page if the
Auto Recovery
function is not enabled.
Auto Recovery Threshold
: Enter the voltage level at which the selected
output will automatically be reconnected. This value must be at least 0.5V
above the
Load-Shedding Threshold
voltage.
NOTE:
Outputs that have been disabled on the Status & Control Page will reconnect
automatically if Load-Shedding Auto Recovery is enabled for that output. To prevent this,
ensure that Load-Shedding Auto Recovery is not enabled.
Output Over-Current Alarm:
Over-Current Threshold
: Enter the over-current level. Output current above
this level for at least 5s will trigger the Over-Current Alarm. Disable this
alarm by setting the threshold to 0A.
Activate Form-C Contact
: Checking this box will cause the Alarm relay to
trigger for an over-current condition.
Send E-mail
: Checking this box will cause the unit to send an output Over-
Current alarm e-mail to the assigned address entered on the
E-mail Setup
page.
Output Under-Current Alarm:
Under-Current Threshold
: Enter the under-current level. Output current
below this level for at least 5s will trigger the Under-Current Alarm. Disable
this alarm by setting the threshold to 0A.