Metering System Quickstart Guide
Electro
Industries/GaugeTech
™
Powered by Innovation™
8. Click Communications (see instructions below).
9. Click CT, PT Ratios and System Hookup (see instructions below).
10.Click Time Settings (see instructions on the next
page.
Communications Settings:
COM 1: RS485/ Ethernet/WIFI (optional)
Address: 1-247; Baud Rate: 57600;
Protocol: Modbus RTU/Modbus ASCII;
Response Delay: 0-750ms; Parity: Odd, Even or
None
COM 2: USB port
NOTE:
The USB port settings are fixed.
COM 3: RS485
Address: 1-247; Protocol: Modbus RTU/ASCII
Baud Rate: 9600, 19200, 38400, 57600
Response Delay: 0-750ms
NOTE:
Click the (1)Default to Ethernet or
(2)Default to Display button to set either the
(1)Ethernet settings for COM1 or (2)Display set-
tings for COM3, to their default values.
CT, PT Ratios and System Hookup:
Note that the
settings you see on the screen depend on your
MP200 unit’s circuit configuration. The top screen is
for an MP200 unit with the single phase circuit con-
figuration (MP200-S). The second screen is for an
MP200 unit with the three phase circuit configura-
tion (MP200-Y). The bottom screen is for an MP200
unit with the 2 CT Delta circuit configuration.