6.4 Cooling mode function requirement
6.4.1. The compressor will be activated by sensing the difference between setting temperature and the
actual ambient room temperature.
6.4.2. The compressor operates as below:
(TA-Ts)
℉
+2
0
Operation conditon
compressor off with a delay of 1 minute
compressor on
When TA
≤
TS, compressor off
When T1>TS+2
F, compressor on
6.4.3. The ION/TIMER/SLEEP/ENERGY SAVE/FOLLOW ME functions are valid at the cooling mode.
6.4.4. Auto-defrosting function protection as below:
When TE is lower, it means that the evaporator frosts. Then the unit starts defrosting, and the
indoor fan keeps working at the moment. When the temperature is up, the unit stops defrosting.
TE
℉
55
30
compressor off
when TE is lower than 30
℉
lasting for 5 seconds
compressor on