9.3.5 Open circuit or short circuit of temperature sensor diagnosis and solution(E5)
Error Code
E5
Malfunction decision
conditions
If the sampling voltage is lower than 0.06V or higher than 4.94V,
the LED will display the failure.
Supposed causes
●
Wiring mistake
●
Sensor faulty
Trouble shooting:
Check the connections
between temperature
sensor and main PCB.
Are the connections
good?
Correct the connections.
No
Yes
Yes
Replace indoor or
outdoor main PCB.
Replace the sensor and
check if the problem happen
again?
Check the resistance value
of the sensor via
table1(p64)and table
2(p65), is it normal?
No
45
Innovair Corporation
Nexxos Inverter
Summary of Contents for NIN1225C2V31
Page 6: ...2 2 Part names of Indoor Outdoor units 4 Innovair Corporation Nexxos Inverter ...
Page 13: ...5 Wiring Diagram 5 1 Indoor Unit NIN516C2V31 ID 11 Innovair Corporation Nexxos Inverter ...
Page 14: ...NIN522C2V31 ID 12 Innovair Corporation Nexxos Inverter ...
Page 15: ...NIN1225C2V31 ID 13 Innovair Corporation Nexxos Inverter ...
Page 16: ...5 2 Outdoor Unit NIN516C2V31 OD 14 Innovair Corporation Nexxos Inverter ...
Page 17: ...NIN522C2V31 OD 15 Innovair Corporation Nexxos Inverter ...
Page 18: ...NIN1225C2V31 OD 16 Innovair Corporation Nexxos Inverter ...
Page 19: ...For NIN516C2V31 OD 17 Innovair Corporation Nexxos Inverter ...
Page 20: ...For NIN522C2V31 OD 18 Innovair Corporation Nexxos Inverter ...
Page 21: ...For NIN1225C2V31 OD 19 Innovair Corporation Nexxos Inverter ...
Page 39: ...9 2 Outdoor unit error display For NIN516C2V31 OD 37 Innovair Corporation Nexxos Inverter ...
Page 49: ...P U P V 47 Innovair Corporation Nexxos Inverter ...
Page 50: ...P W P N 48 Innovair Corporation Nexxos Inverter ...