Drain hose
Tape
Outlet pipe
Insulating pipe
Torque wrench
Open-end
wrench
Indoor pipe
Pipe
Union nut
Union nut
Pipe joint
Pipe
Refer to the following table for wrench moment of force
:
Drain hose
Insulating pipe
5-10
°
Φ
2 1/6 inch
Indoor
Outdoor
(1) Pay attention to dust prevention and take relevant safety
measures when opening the hole.
(2) The plastic expansion particles are not provided and should
be bought locally.
(1) Add insulating pipe in the indoor drain hose in order to
prevent condensation.
(2) The plastic expansion particles are not provided.
(As show in Fig.10)
9K/12K
Fig.2
Fig.5
Fig.6
Fig.7
Fig.8
Fig.9
Fig.10
Fig.3
Fig.4
5. Connect the Pipe of Indoor Unit
(1) Aim the pipe joint at the corresponding bellmouth.(As show
in Fig.5)
(2) Pretightening the union nut with hand.
(3) Adjust the torque force by referring to the following sheet.
Place the open-end wrench on the pipe joint and place the
torque wrench on the union nut. Tighten the union nut with
torque wrench.(As show in Fig.6)
(4) Wrap the indoor pipe and joint of connection pipe with
insulating pipe, and then wrap it with tape.(As show in Fig.7)
6. Install
D
rain Hose
(1) Connect the drain hose to the outlet pipe of indoor unit.(As
show in Fig.8)
(2) Bind the joint with tape.(As show in Fig.9)
4. Outlet Pipe
(1) The pipe can be led out in the direction of right, rear right,
left or rear left.(As show in Fig.3)
(2) When selecting leading out the pipe from left or right, please
cut off the corresponding hole on the bottom case.(As show in
Fig.4)
(2) Open a piping hole with the diameter of 2 1/6
" (or 2 3/4")
on the
selected outlet pipe position.
In order to drain
smoothly, slant
the piping hole on the wall slightly downward
to the outdoor
side with the gradient of 5-10°.(As show in
Fig.2)
Note:
Note:
(3) Fix the wall-mounting frame on the wall with tapping screws
pulling the frame. If the plastic expansion particle is loose,
3. Install Wall-mounting Frame
(1) Choose the position of piping hole according to the direction
of outlet pipe. The position of piping hole should be a little
lower
than the wall-mounted frame.(As show
below
)
Hex nut diameter(inch) Tightening torque(ft·Ibf)
Φ1/4
11.10~14.75
Φ3/8
20.12~29.50
Φ1/2
33.19~40.56
Φ5/8
44.24~47.94
Φ3/4
51.32~55.31
Left
Rear left
Right
Rear right
Cut off
the hole
Left
Right
Outlet
pipe
Drain hose
Left
Wall
Φ2 1/6
Φ2 1/6
Right
Mark in the middle of it
Level meter
Rear piping hole
Wall
Space
to the
wall
above
6inch
Space
to the
wall
above
6inch
Rear piping hole
3
2
SERVICE MANUAL
Innovair Elite Mini Split
18K/24K
Left
Wall
2 3/4inch
Right
Mark in the middle of it
Level meter
Rear piping hole
Wall
Space
to the
wall
above
150mm
Space
to the
wall
above
150mm
2 3/4inch
Rear piping hole