background image

D100-68-00 

I56-1684-007R

24V

120

VAC

220/240

VAC

9

10

A

B

C

AVAILABLE POWER INPUTS

ALARM AUXILIARY CONTACTS

FOR FAN SHUTDOWN, ETC.

16

6

17

7

18

8

N.C.

C.

N.O.

N.O.

C.

N.C.

ALARM AUXILIARY CONTACTS SHOWN IN

STANDBY. CONTACTS TRANSFER DURING

ALARM AS INDICATED BY THE ARROWS.

SUPERVISORY TROUBLE CONTACTS

TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY.

CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS

REMOVED OR WHEN TAMPER FEATURE TIMES OUT. OPEN 

CONTACTS SIGNAL TROUBLE CONDITION TO PANEL.

24V

220/240

VAC

9

10

A

B

C

AVAILABLE POWER INPUTS

ALARM AUXILIARY CONTACTS

FOR FAN SHUTDOWN, ETC.

16

6

17

7

18

8

N.C.

C.

N.O.

N.O.

C.

N.C.

ALARM AUXILIARY CONTACTS SHOWN IN

STANDBY. CONTACTS TRANSFER DURING

ALARM AS INDICATED BY THE ARROWS.

SUPERVISORY  TROUBLE CONTACTS

TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY.

CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS

REMOVED OR WHEN TAMPER FEATURE TIMES OUT. OPEN 

CONTACTS SIGNAL TROUBLE CONDITION TO PANEL.

14

3

3

14

4

5

ALARM

INITIATION

CONTACTS

CONTACTS SHOWN

OPEN IN STANDBY.

CONTACTS CLOSE

IN ALARM.

4

5

ALARM

INITIATION

CONTACTS

CONTACTS SHOWN

OPEN IN STANDBY.

CONTACTS CLOSE

IN ALARM.

ALARM

INITIATION

LOOP

UL LISTED 4-WIRE

CONTROL PANEL

FIRST DETECTOR IN THE LOOP

DH100ACDCI

LAST DETECTOR IN THE LOOP

DH100ACDCI

EOL RESISTOR

SPECIFIED BY

PANEL MANUFACTURER

CONNECT POWER SOURCE

TO APPROPRIATE TERMINALS

OF EACH DETECTOR. SEE

SPECIFICATIONS FOR

ADDITIONAL POWER SUPPLY

INFORMATION.

FOR WIRING OF AUXILIARY

DEVICES, REFER TO

MANUFACTURER'S

INSTALLATION INSTRUCTIONS

OR CONTACT MANUFACTURER.

NOTE:

 THE SUPERVISORY RELAY NOW

PROVIDES A "FORM C" CONTACT FOR

CUSTOMIZED APPLICATIONS.

FOR STANDARD APPLICATIONS, ONLY

THE "NO" CONTACT IS USED

POWER INPUTS ACCEPT

24 VDC, 24 VAC  50-60 HZ,

120 VAC 50-60 HZ, OR

220/240 VAC 50-60 HZ.

CONNECT POWER SOURCE

TO APPROPRIATE TERMINALS

OF EACH DETECTOR.      

AUX. CONTACT RATINGS

10A @ 30 VDC RESISTIVE

10A @ 250 VAC

100mA MINIMUM @ 5 VDC

1/4 HP @ 240 VAC

1/8 HP @ 120 VAC

NOT INTENDED FOR

CONNECTION TO CONTROL

PANELS.

TROUBLE CONTACT RATING

2.0 A @ 30 VDC resistive

2.0 A @ 125 VAC resistive

+

120

VAC

CAUTION

Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections.

Figure 8. Wiring diagram for DH100ACDCI to APA451:

H0182-00

H0155-01

Figure 7. System wiring diagram for 4-wire duct smoke detectors:

15

19

14

3

20

1

3

2

Alarm Signal

Aux. Power +

Sup. N. O.

Sup. COM

Aux. Power –

NOTE:  Wiring diagram shown is for DH100ACDCI 4-wire duct
 

smoke detector system equipped without a control panel.

Alarm

Power

Common

APA451

DH100ACDCI

NOTE:  A trouble condition is indicated when the green LED
 

is not illuminated.

Figure 9. Wiring diagram for DH100ACDCI to 
RTS451KEY:

15

19

14

3

20

2

11

2

6

1

Alarm Signal

Aux. Power +

Sup. N. O.

Sup. COM

Aux. Power –

Reset

Test

(Red LED) Alarm

(Green LED)
Power

DH100ACDCI

RTS451/RTS451KEY

5

4

3

*

For RTS451KEY
only without a
control panel.

*

Important Interconnect Notes

•  When  using  the  interconnect  feature,  all  inter-

connected  units  must  be  powered  with  the 
same, independent supply.

•  Polarity  must  be  maintained  throughout  the 

interconnect wiring. Connect terminal 12 on unit 
1 to terminal 12 on unit 2 and so on. Similarly, 
connect  terminal  1  on  unit  1  to  terminal  1  on 
unit 2 and so on.

•  Up to 10 units may be interconnected.

Figure 10. Multiple fan shutdown (interconnect):

1

6

12

16

A

B

C

FAN

CONTROL

SYSTEM

CONTROL

POWER OR

THERMOSTAT

1

6

12

16

A

B

FAN

CONTROL

SYSTEM

CONTROL

POWER OR

THERMOSTAT

DETECTOR 1

C

DETECTOR 2

1

6

12

16

A

B

FAN

CONTROL

SYSTEM

CONTROL

POWER OR

THERMOSTAT

C

DETECTOR 10

OUT TO

10 DETECTORS

MAXIMUM

H0518-00

H0500-00

Summary of Contents for DH100ACDCI

Page 1: ...hut down These detectors are not designed for 2 wire applications For testing the alarm can be enabled by a magnet activated test switch or by the optional remote test station The duct smoke detector latches into alarm state when an alarm occurs A green LED flashes to indicate power a red LED signals local alarm indication and optional accessories offer a variety of annuncia tion capabilities The ...

Page 2: ...les as indi cated in Figure 4 D100 68 00 2 I56 1684 007R 4 Figure 1 Exploded View Of Duct Smoke Detector Components FOAM GASKETS PLASTIC SAMPLING TUBE CONDUIT HOLES DETECTOR HOUSING TERMINAL STRIP DETECTOR COVER SAMPLING TUBE FILTERS PLASTIC SAMPLING TUBE SELF TAPPING SCREW POWER BOARD DETECTOR BOARD COVER MOUNTING SCREWS H0401 00 H0110 00 5 Installation Sequence 5 1 Verify Duct Air Flow Direction...

Page 3: ...t the end opposite the duct smoke detector Figure 5 Tube mounting configurations with varying air flow direction AIR FLOW DIRECTION DETECTOR HOUSING DOTS INDICATE POSITION OF SAMPLING TUBE HOLES AIR FLOW DIRECTION DETECTOR HOUSING SAMPLING TUBE EXHAUST TUBE AIR FLOW DIRECTION EXHAUST TUBE SAMPLING TUBE SAMPLING TUBE EXHAUST TUBE DETECTOR HOUSING AIR FLOW DIRECTION DETECTOR HOUSING A B C D HORIZONT...

Page 4: ... between interconnected detectors or from detectors to auxiliary devices it is usually recommended that single conductor wire be no smaller than 18 gauge The duct smoke detector terminals accommodate wire sizes up to 12 gauge The last foot of conduit should be flexible conduit available in electrical supply houses which facilitates easier installation and puts less strain on the conduit holes in t...

Page 5: ... RTS451KEY is not required when these accessories are used with the DH100ACDCI detectors The functionality of the magnetic coil has been designed into the circuitry of the new In novair duct smoke detectors 6 2 2 3 SSK451 Multi Signaling Accessory The System Sensor SSK451 Multi Signaling accessory combines a sounder feature with a key activated test and reset function Green amber and red LEDs prov...

Page 6: ...S ACCEPT 24 VDC 24 VAC 50 60 HZ 120 VAC 50 60 HZ OR 220 240 VAC 50 60 HZ CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR AUX CONTACT RATINGS 10A 30 VDC RESISTIVE 10A 250 VAC 100mA MINIMUM 5 VDC 1 4 HP 240 VAC 1 8 HP 120 VAC NOT INTENDED FOR CONNECTION TO CONTROL PANELS TROUBLE CONTACT RATING 2 0 A 30 VDC resistive 2 0 A 125 VAC resistive 120 VAC CAUTION Do not loop wire under termin...

Page 7: ...ination of accessories may be used such that the given accessory loads are 60 mA or less in the standby state 110 mA or less in the alarm state TROUBLE n a n a n a n a 9mA Max D100 68 00 7 I56 1684 007R Figure 11 Wiring diagrams for optional accessories H0402 01 15 ALARM SIGNAL 3 14 2 RESET 11 TEST 20 AUX POWER 19 AUX POWER SSK451 FIELD INSTALLED JUMPER FOR TEMPORAL PATTERN SUPERVISORY CONTACT NO ...

Page 8: ...60 Hz CURRENT REQUIREMENTS USING NO ACCESSORIES Max standby current 15 mA 35 mA RMS 25 mA RMS 15 mA RMS Max alarm current 70 mA 125 mA RMS 35 mA RMS 25 mA RMS CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm auxiliary contacts DPDT 10A 30 VDC 10A 250 VAC 1 4 HP 240 VAC 1 8 HP 120 VAC Trouble contacts SPDT 2 0A 30 VDC resistive 2 0A 125 VAC resistive Note Alarm auxiliary c...