31
TOUCHPAD AND REMOTE CONTROL
Terminal block position
A
Terminal block
A
The spring terminals allow the connection of rigid or flexible
cables with sections from 0.2 to 1 mm². For cables provided
with lugs with plastic collar the maximum section is reduced
to 0,75 mm².
Connection to the PCB
8 mm
0.2 - 1 mm2
For the connection:
– remove a portion of the insulation from the end of the
cable
– follow the indication on the connection diagram
– insert the cable into the spring terminal
– insert the cable completely
– make sure they are properly fixed by pulling them slightly
CP presence contact input connection
Trough this contact it is possible connect an external device
that inhibits the operation of the device, for example:
• opening window contact
• remote on/off
• infrared presence sensor
• enabling badge
• remote change of season
Function
When the contact connected to the CP input is closed, all the
users connected will be switched off.
At the touch of a button on the display the symbol
flash-
es.
It is forbidden connect in parallel the CP input to one of
another electronic board. Use separate contacts.
RS485 Serial Connection
The wall-mounted remote control can be connected through
a RS485 serial line to one or more device, for a maximum of
30. The devices must be equipped with an electronica card
suitable for remotization.
For the connection:
– follow the indication on the connection diagram
– connect respecting the indication "A" and "B"
Use a bipolar shielded cable suitable for the RS485 serial
connection with a minimum section of 0,35 mm².
Keeping the bipolar cable separate from power supply
cables.
Chase out the wall in order to minimize the length of the
leads.
Complete the line with the 120 Ω resistance.
It is forbidden make "star" connections.