11
S
I
U
2.10
H2
H4
AIR
N540022B
A
2.9
EN
Continuous modulation circuit board for connecting remote thermostat
(only for models ESE645 - ESE648)
LED Indications (Ref. A) (only for models ESE645 - ESE648)
The circuit board for remote control is for all functions of
the fan coil system from the wall-mounted remote control
EDA/EDB649 - EWG/EWW649.
A remote control can be connected to a maximum of
30 fan coils that will be controlled in broadcast mode
(simultaneous commands to all fan coils).
It can be installed on all versions, the board has a green
LED that indicates the operational state and any anomalies.
The main operational parameters, the set point and the
room temperature are transmitted from the wall-mounted
remote control EDA/EDB649 - EWG/EWW649 to all
terminals connected to the network, allowing unified
operation.
Refer to the instructions for this control for use of the fan
coils.
The 10 kΩ water temperature probe positioned in the
device battery regulations the minimum level when heating
(30°C) and the maximum level when cooling (20°C).
Green LED: Indicates that the unit is
operational. Flashing indicates an anomaly.
LED off: unit is off or has no power.
Segnalazioni d'errore
Error
Display
Communication error. The circuit board expects continuous information exchange on the serial line
with the wall-mounted control EDA/EDB649 - EWG/EWW649. If this exchange is lost for more than
5 minutes, an error warning is displayed and the unit deactivated.
6 f pause
Problem with fan motor (e.g. blockage caused by foreign objects, faulty rotation sensor).
2 f pause
Water temperature probe fault for 2-tube versions (H2).
In this case, ensure that the probe installed is 10 kΩ.
3 f pause
Cold water temperature probe fault for 4-tube versions (H4).(Only for ESE648) positioned on the
main battery.
5 f pause
GRID contact open
Continuous rapid
flashing
Water demand detected by probe H2 insufficient (above 20°C when cooling, below 30°C when
heating). Stops the fan until the temperature returns to a suitable level to satisfy the demand*.
1 f pause
Only for board ESE648 (4-tube machines): cold water demand detected by probe H4 insufficient
(above 20°C). Stops the fan until the temperature returns to a suitable level to satisfy the demand*.
4 f pause
* If after having powered the board the water probe is
detected, start-up takes place with the minimum and
maximum water temperature thresholds.
The board also has a function when there is no probe, in
such cases the fan stop thresholds are ignored.