DS 1.29 - SENW5x - Wall Mounted Temperature Detector

December 2015

SENW5x Detector Connection Identification

SENW58x Connection Diagram - 24VDC

SENW58x Connection Diagram - 24VAC

SENW58x

GND

VIN

OVR

STPT

Temp

Temp

10VDC / 0V Input

0 to 10VDC Output

Thermistor (Temp +)

Thermistor (Temp -)

0V / GND

24VAC

From

Power Supply

From Controller

Output

(0VDC=off, 10VDC=on)

To Controller

 Inputs

SENW58x

GND

VIN

OVR

STPT

Temp

Temp

10VDC / 0V Input

0 to 10VDC Output

Thermistor (Temp +)

Thermistor (Temp -)

0V / GND

24VDC

From

Power Supply

From Controller

Output

(0VDC=off, 10VDC=on)

To Controller

 Inputs

Maximum terminal cable entry is 2.5mm² (stranded conductor).

FCC Class A Notice

This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:

1.  This device may not cause harmful interference.
2.  This device must accept any interference received, including interference that may cause undesired operation.

Note

 – 

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable 

protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses and can radiate radio frequency energy and, if not 

installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. 

Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. Modifications to this 
device, may void the authority granted to the user by the FCC to operate this equipment.

Polarity MUST be observed when connecting power.

Earth screens at controller only.

• When using 24VDC to power the device, a single shielded cable 

may be used for power and control signals.

• Link is required if override is not used.
• Maximum terminal cable entry is 2.5mm² (stranded conductor).

Polarity MUST be observed when connecting power.

Earth screens at controller only.

• When using 24VAC to power the device, separate cables must be 

used for power and control signals.

• Link is required if override is not used.
• Maximum terminal cable entry is 2.5mm² (stranded conductor).

Gnd

VIN

OVR

STPT

Temp

Temp

SENW58x Detector

CONNECTOR INFORMATION
Connector

Description

Gnd

Power Common / Neutral

VIN

+ Power 24VDC or 24VAC 

±

10%

OVR

Override Input
(10VDC = Occupied, 0VDC = Unoccupied)

STPT

Setpoint Output
0 to 10VDC (Ref. to GND Common)

Temp

Temperature Sensor (Isolated)

Temp

SENW58x

SENW51

Temp

Temp

3.45" (87.6mm)

0.32" (8mm)

SENW51 Detector

CONNECTOR INFORMATION
Connector

Description

Temp

Temperature Sensor (Isolated)

Temp

Summary of Contents for SENW51

Page 1: ...nclosure design Wall mounted Displays Temperature and Setpoint at a glance Onboard temperature sensor Displays Fahrenheit F or Celsius C Push button interface for a Temperature setpoint adjustment b Occupancy override Display available on SENW58 model only Temperature setpoint adjustment and override available on SENW58 model only Installation Wiring The SENW5x detector should be installed in an e...

Page 2: ...ATURE SENSOR Resistance NTC 10 000Ω thermistor 10K 2 Accuracy 0 36 F 0 2 C from 32 to 158 F 0 to 70 C Inputs and Outputs AVAILABLE OUTPUTS Temperature Temperature Temp Resistance 10K 2 thermistor Isolated Setpoint STPT 0 to 10VDC configurable setpoint signal ref to power GND OCCUPIED INPUT Occupancy OVR Occupied 10VDC Man displayed Unoccupied 0VDC Man not displayed ref to power GND Controls and Di...

Page 3: ...Temp and Setpoint P7 Secondary Display Indicates Temperature Setpoint P8 The display can be adjusted for resolutions of 0 1 0 5 or 1 The backlit display has two modes Active and Inactive Active When a button press is detected the display will illuminate Inactive When no button activity is detected for 5 seconds the display will become dull The is displayed on the SENW58 to indicate Occupied or Uno...

Page 4: ... or disables the adjustment of the setpoint This setting locks the setpoint at the current value and disables the Up Down buttons This setting enables the setpoint to be changed by the user using the Up Down buttons Factory Default Parameter 6 Occupancy Lockout This parameter enables or disables the override button function This setting disables the Override button This setting enables the Overrid...

Page 5: ...ates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense Modifications to this device may void the autho...

Page 6: ...61 7 3421 9100 Fax 61 7 3421 9101 Email sales innotech com au www innotech com au The INNOTECH device and the word INNOTECH are registered or unregistered trademarks of Mass Electronics Pty Ltd in Australia USA and other countries Configurations are available from the Innotech Website by clicking here Please note that the Fault Limits should be set as shown Please note that the Fault Value should ...

Reviews: