background image

© MASS ELECTRONICS Pty Ltd  2014

Page 2

DS 1.29 - SENW5x - Wall Mounted Temperature Detector

December 2015

Specifications

POWER SUPPLY REQUIREMENTS (SENW58 Only)

Power Input

24VDC or 24VAC ±10% @ 50/60Hz

Power Consumption

10mA @24VDC (80mA w/ backlight on)

Polarity MUST be observed when connecting power.

If using 24VAC, the data and power cabling should be segregated and 

data run in screened cable (as shown on page 5).

ENVIRONMENTAL

Operating Temperature

32°F to 104°F (0 to 40°C)                        

non-condensing

Storage Temperature

32°F to 122°F (0 to 50°C)  

non-condensing

ENCLOSURE

Housing is moulded from flame retardant plastics recognised by UL  

as UL94-V0. The housing is designed to maximise airflow to the onboard 

sensors.  It should be mounted with a standard vertical C-Clip, or on a 

standard wall enclosure.
Colour

Grey / White

Dimensions(Maximum)

(W)2.76" x (H)4.76" x (D)1.6" 

[70mm x 121mm x 41mm]

APPROVALS

EN61326-1:2013 for CE Marking and RCM Labelling
Title 47 CFR, Part 15, Subpart B, Class A for FCC Verification

Onboard Sensor

TEMPERATURE SENSOR

Resistance

NTC 10,000Ω thermistor (10K-2)

Accuracy

±0.36°F (0.2°C) 
from 32 to 158°F (0 to 70°C)

Inputs and Outputs

AVAILABLE OUTPUTS

Temperature

Temperature (Temp) Resistance,  

10K-2 thermistor (Isolated)

Setpoint (STPT)

0 to 10VDC = configurable setpoint 

signal (ref. to power GND)

OCCUPIED INPUT

Occupancy (OVR)

Occupied = 10VDC ("Man" displayed)
Unoccupied = 0VDC  

("Man" not displayed)    
(ref. to power GND)

Controls and Display

CONTROLS (SENW58 Only)

Setpoint

Up and Down Buttons

Override / Select

Single Button

DISPLAY (SENW58 Only)

Backlit LCD for Temperature, Setpoint and Override

Primary Display

Four Numeric Digits 0.75" (19mm) high 

with one selectable decimal

Secondary Display

Four Numeric Digits 0.5" (12.7mm) high 

with one selectable decimal

Icons

            /            /             

Display Size (Width x Height)

1.6" x 1.2" (40mm x 30mm)

Digit Resolution

0.1, 0.5 or 1

Units

°F, °C

Temperature Offset Range

±10

SET

Up
Down

Override / 

Select

Primary  

Display
Secondary  

Display

DAY

MONTH

ON

SET

STARTSTOP

ppm

kWh

Setpoint Indicator

Numeric / Text 

Primary Display

Override Status

Numeric / Text 

Secondary Display

Temperature 

Indicators

1.6” (41mm)

1” 

(26mm)

0.6” 

(15mm)

4.76" (121mm)

2.76" (70mm)

SENW5x Dimensions and Identification

(SENW58F Shown)

SENW58 LCD Display

1" 

(26mm)

0.6" 

(15mm)

1.6" (41mm)

Summary of Contents for SENW51

Page 1: ...nclosure design Wall mounted Displays Temperature and Setpoint at a glance Onboard temperature sensor Displays Fahrenheit F or Celsius C Push button interface for a Temperature setpoint adjustment b Occupancy override Display available on SENW58 model only Temperature setpoint adjustment and override available on SENW58 model only Installation Wiring The SENW5x detector should be installed in an e...

Page 2: ...ATURE SENSOR Resistance NTC 10 000Ω thermistor 10K 2 Accuracy 0 36 F 0 2 C from 32 to 158 F 0 to 70 C Inputs and Outputs AVAILABLE OUTPUTS Temperature Temperature Temp Resistance 10K 2 thermistor Isolated Setpoint STPT 0 to 10VDC configurable setpoint signal ref to power GND OCCUPIED INPUT Occupancy OVR Occupied 10VDC Man displayed Unoccupied 0VDC Man not displayed ref to power GND Controls and Di...

Page 3: ...Temp and Setpoint P7 Secondary Display Indicates Temperature Setpoint P8 The display can be adjusted for resolutions of 0 1 0 5 or 1 The backlit display has two modes Active and Inactive Active When a button press is detected the display will illuminate Inactive When no button activity is detected for 5 seconds the display will become dull The is displayed on the SENW58 to indicate Occupied or Uno...

Page 4: ... or disables the adjustment of the setpoint This setting locks the setpoint at the current value and disables the Up Down buttons This setting enables the setpoint to be changed by the user using the Up Down buttons Factory Default Parameter 6 Occupancy Lockout This parameter enables or disables the override button function This setting disables the Override button This setting enables the Overrid...

Page 5: ...ates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense Modifications to this device may void the autho...

Page 6: ...61 7 3421 9100 Fax 61 7 3421 9101 Email sales innotech com au www innotech com au The INNOTECH device and the word INNOTECH are registered or unregistered trademarks of Mass Electronics Pty Ltd in Australia USA and other countries Configurations are available from the Innotech Website by clicking here Please note that the Fault Limits should be set as shown Please note that the Fault Value should ...

Reviews: