Booster Parameters
Booster Parameters
B 09
P
1 ~ 200
It is relevant to ‘P’ out of PID
control parameters. PID I-Gain 1
second means the time required
for the output power to be
accumulated to 1.0[Hz] when 200
bar errors are maintained.
25
25
B 10
I
1 ~ 200
It is relevant to ‘I’ out of PID
control parameters. PID I-Gain 1
second means the time required
for the output power to be
accumulated to 1.0[Hz] when 200
bar errors are maintained.
40
40
B 11
D
1 ~ 200
It is relevant to ‘D’ out of PID
control parameters. PID I-Gain 1
second means the time required
for the output power to be
accumulated to 1.0[Hz] when 200
bar errors are maintained.
40
40
B 12
Auto Reset
Time
0 ~ 20
It can applied only for OC, OL, OV,
LV faculties.
(when the Auto reset occures,
there is approx. 1min. delay time.
If the delay time is too short, the
trip will occur)
5
5
B 13
Initial
Operation
Status
0 ~ 2
- 0 : Stop
- 1 : Run
- 2 : latest default
2
2
B 14
B 15
B 16
B 17
VERSION