Alarm
Code
Description
Solution
0800H
Code 1: 0x0020H
Hardware fault in the DC/DC. phase
Check the installation in the DC and AC part.
Disconnect the DC and AC inverter. Wait until the LEDs
go off and re-connect.
If the error persists, contact the Technical Service.
Code 1: 0x0040H
HW fault in the DC/AC. conversion
phase
Code 1: 0x0080H
Hardware fault in the VAC sensor.
Code 1: 0x0100H
Hardware fault in the residual
current sensor.
10000H
-
Inverter overload. The inverter
is supplying more power than
its maximum power in the
consumption grid.
Check the installation consumptions.
20000H
-
Short circuit in the consumption
grid output.
Check the consumption grid installation.
80000H
Code 2: 0x0200H
Error communicating with the
storage system manager.
Check the CAN communication wiring of the storage
system management system.
Make sure that the storage system starts via the
display (see section
103
Troubleshooting
Ingeteam
ABH2013IQM01_A - Installation and Operation Manual