Table 13.
Diagnostic Objects Sorted by Object Name (continued)
Object
Identifier
Binary Input
Object Name
Description
Notification
Class
When Exists
BI 35
Diagnostic: Local Zone Heat Setpoint Fail
Diagnostic: Local Zone Heat Setpoint
Fail
002 – Service
Required
Always
BI 147
Diagnostic: Maintenance Required
Diagnostic: Maintenance Required
002 – Service
Required
Always
BI 242
Diagnostic: Min OA Flow Setpoint Fail
Diagnostic: Min OA Flow Setpoint Fail
002 – Service
Required
With RTVM
installed
BI 310
Diagnostic: Mixed Air Temp Low Limit
Cycle Active
Diagnostic: Mixed Air Temp Low Limit
Cycle Active
004 -
Information
Always
BI 95
Diagnostic: Mixed Air Temp Sensor
Failure
Diagnostic: Mixed Air Temp Sensor
Failure
002 – Service
Required
With RTEM
installed
BI 279
Diagnostic: Mod Dehumid Config Error
Diagnostic: Mod Dehumid Config Error
004 –
Information
Always
BI 239
Diagnostic: Morning Warmup Setpoint
Fail
Diagnostic: Morning Warmup Setpoint
Fail
002 – Service
Required
Always
BI 261
Diagnostic: No Flame Sensed on heat call
Diagnostic: No Flame Sensed on heat
call
004 –
Information
With Gas Heat
installed
BI 37
Diagnostic: OA Humidity Sensor Failure
Diagnostic: OA Humidity Sensor Failure
002 – Service
Required
With RTEM
installed
BI 32
Diagnostic: OA Temperature Sensor Fail
Diagnostic: OA Temperature Sensor Fail
002 – Service
Required
Always
BI 58
Diagnostic: Return Air Humidity Sensor
Fail
Diagnostic: Return Air Humidity Sensor
Fail
002 – Service
Required
With RTEM
installed
BI 57
Diagnostic: Return Air Temp Sensor Fail
Diagnostic: Return Air Temp Sensor Fail
002 – Service
Required
With RTEM
installed
BI 274
Diagnostic: RTAM Comm Fail
Diagnostic: RTAM Comm Fail
004 –
Information
With RTAM
installed
BI 276
Diagnostic: VSM Comm Fail
Diagnostic: VSM Communication Fail
004 –
Information
With VSM
installed
BI 277
Diagnostic: RTDM Comm Fail
Diagnostic: RTDM Comm Fail
004 –
Information
With RTDM
installed
BI 273
Diagnostic: RTEM Comm Fail
Diagnostic: RTEM Comm Fail
004 –
Information
With RTEM
installed
BI 29
Diagnostic: RTM Zone Temp Sensor
Failure
Diagnostic: Zone Temp Sensor Failure
002 – Service
Required
BI 272
Diagnostic: RTOM Comm Fail
Diagnostic: RTOM Comm Fail
004 –
Information
With RTOM
installed
BI 275
Diagnostic: RTVM Comm Fail
Diagnostic: RTVM Comm Fail
004 –
Information
With RTVM
installed
BI 267
Diagnostic: SA Pressure Dead Band
Failure
Diagnostic: SA Pressure Dead Band
Failure
004 –
Information
With RTAM
installed
BI 268
Diagnostic: SA Pressure PWM Fault
Diagnostic: SA Pressure PWM Fault
004 –
Information
Always
BI 54
Diagnostic: SA Pressure Setpoint Failure
Diagnostic: SA Pressure Setpoint Failure
002 – Service
Required
Always
BI 123
Diagnostic: SA Reheat Setpoint Failure
Diagnostic: SA Reheat Setpoint Failure
002 – Service
Required
Always
BI 265
Diagnostic: SA Reset Amount Failure
Diagnostic: SA Reset Amount Failure
004 –
Information
With RTOM
installed