38
BAS-SVP09F-EN
Table 10.
Diagnostics, Binary Input (continued)
Object
Identifier
Object Name
Description
Notification Class
When Exists
BI 44
Diagnostic: Compressor 2 LPC
Lockout
Diagnostic: Compressor 2 LPC
Lockout
001 – Critical
Always
BI 45
Diagnostic: Coil Temp Sensor #1
Fail
Diagnostic: Coil Temp Sensor 1 Fail 1
002 – Service Required
Always
BI 46
Diagnostic: Coil Temp Sensor #2
Fail
Diagnostic: Coil Temp Sensor 2 Fail
002 – Service Required
Always
BI 47
Diagnostic: Compressor 1 HPC
Lockout
Diagnostic: Compressor 1 HPC
Lockout
001 – Critical
Always
BI 48
Diagnostic: Compressor 2 HPC
Lockout
Diagnostic: Compressor 2 HPC
Lockout
001 – Critical
Always
BI 51
Diagnostic: Heat Failure
Diagnostic: Heat Failure
003 – Advisory
Always
BI 54
Diagnostic: SA Pressure Setpoint
Failure
Diagnostic: SA Pressure Setpoint
Failure
002 – Service Required
Always
BI 55
Diagnostic: Space Pressure
Setpoint Fail
Diagnostic: Space Pressure Setpoint
Fail
002 – Service Required
Always
BI 56
Diagnostic: Space Pressure
Sensor Fail
Diagnostic: Space Pressure Sensor
Fail
002 – Service Required
Always
BI 57
Diagnostic: Return Air Temp
Sensor Fail
Diagnostic: Return Air Temp Sensor
Fail
002 – Service Required
With RTEM installed
BI 58
Diagnostic: Return Air Humidity
Sensor Fail
Diagnostic: Return Air Humidity
Sensor Fail
002 – Service Required
With RTEM installed
BI 59
Diagnostic: Auto - SA High Press
Limit
Diagnostic: Auto - SA High Press Limit
002 – Service Required
Always
BI 74
Diagnostic: SA Temp Cool Setpoint
Fail
Diagnostic: SA Temp Cool Setpoint Fail
002 – Service Required
Always
BI 75
Diagnostic: SA Temp Heat
Setpoint Fail
Diagnostic: SA Temp Heat Setpoint
Fail
002 – Service Required
Always
BI 76
Diagnostic: Dirty Filter
Diagnostic: Dirty Filter
003 – Advisory
Always
BI 83
Diagnostic: CO2 Sensor Failure
Diagnostic: CO2 Sensor Failure
002 – Service Required
With RTEM installed
BI 86
Diagnostic: Velocity Press Sensor
Fail
Diagnostic: Velocity Press Sensor Fail
002 – Service Required
With RTVM version 3
or greater installed
BI 95
Diagnostic: Mixed Air Temp Sensor
Failure
Diagnostic: Mixed Air Temp Sensor
Failure
002 – Service Required
With RTEM installed
BI 106
Diagnostic: Space Humidity
Sensor Fail
Diagnostic: Space Humidity Sensor
Fail
002 – Service Required
With RTEM installed
BI 107
Diagnostic: Entering Evap Temp
Sensor Fail
Diagnostic: Entering Evap Temp
Sensor Fail
002 – Service Required
Always
BI 123
Diagnostic: SA Reheat Setpoint
Failure
Diagnostic: SA Reheat Setpoint
Failure
002 – Service Required
Always
BI 125
Diagnostic: Dehumid Setpoint
Failure
Diagnostic: Dehumid Setpoint Failure
002 – Service Required
With RTOM installed
BI 147
Diagnostic: Maintenance Required
Diagnostic: Maintenance Required
002 – Service Required
Always
BI 148
Diagnostic: Unit Communications
Failure
Diagnostic: Unit Communications
Failure
002 – Service Required
Always
BI 151
Diagnostic: Drain Pan Overflow
Diagnostic: Drain Pan Overflow
004 – Information
With RTOM installed
BI 239
Diagnostic: Morning Warmup
Setpoint Fail
Diagnostic: Morning Warmup Setpoint
Fail
002 – Service Required
Always
BI 242
Diagnostic: Min OA Flow Setpoint
Fail
Diagnostic: Min OA Flow Setpoint Fail
002 – Service Required
With RTVM installed