BAS-SVP09F-EN
35
Table 7. Multistate Input (continued)
BCI-R
Object
Identifier
Object Name
Description
Object States
*not all states apply to all
equipment
When Exists
MI 23
Heating Setpoint Source
Indicates the source of the
space heating setpoint.
1= RTM Zone Sensor
2= Night Setback Panel
3= Human Interface
4= GBAS 0-5V
5= BAS/Network
6= GBAS 0-10V
Always
MI 24
Timed Override Status
Timed override request or
cancel from zone sensor.
1 = Idle
2 = On
3 = Cancel
Always
MI 25
Cool Output 1
Indicates the commanded
state of cooling output 1.
1 = Off
2 = On
3 = Not Present
Always
MI 26
Cool Output 2
Indicates the commanded
state of cooling output 2.
1 = Off
2 = On
3 = Not Present
Always
MI 29
Heat Output 1
Indicates the commanded
state of heating output 1.
1 = Off
2 = On
3 = Not Present
Always
MI 30
Heat Output 2
Indicates the commanded
state of heating output 2.
1 = Off
2 = On
3 = Not Present
Always
MI 31
Heat Output 3
Indicates the commanded
state of heating output 3.
1 = Off
2 = On
3 = Not Present
Always
MI 32
Heat Output 4
Indicates the commanded
state of heating output 4.
1 = Off
2 = On
3 = Not Present
Always
MI 35
Primary Filter Status
Indicates the primary filter
media state.
1 = Clean
2 = Dirty
3 = Not Present
Always
MI 37
Supply Fan Proving
Status
Indicates the current state of
the supply fan.
1= Off
2= On
3= Not Present
Always
MI 38
Exhaust Fan Status
Indicates the commanded
state of the exhaust fan.
1 = Off
2 = On
3 = Not Present
With RTEM Installed
MI 39
Exhaust Fan Proving
Status
Indicates if the unit exhaust
fan is off or on.
1= Off
2= On
3= Not Present
With RTOM installed (Only
activates with RTEM
installed)
MI 41
Supply Fan Status
Indicates the state of the
supply fan.
1 = Off
2 = On
3 = Not Present
Always
MI 43
Outdoor Damper Status
Indicates the operating state of
the outdoor damper.
1 = At or Below Minimum
Position
2 = Above Minimum Position
3 = Not Present
With RTEM Installed