L-Series Service Manual
116
Electrically Locking
L9080 EL Electrically Locked (Fail Safe):
Outside trim is continuously locked electrically.
The latchbolt is retracted by a key outside or by the
knob/lever inside. Switch or power failure allows the
outside knob/lever to retract the latchbolt. The auxiliary
latch deadlocks the latchbolt when the door is closed.
The inside knob/lever is always free for immediate exit.
L9080 EU Electrically Unlocked (Fail Secure):
Outside trim is unlocked electrically. The latchbolt is retract-
ed by a key outside or by knob/lever inside. The auxiliary
latch deadlocks the latchbolt when the door is closed. The
inside knob/lever is always free for immediate exit.
Request to Exit (RX) Feature*:
A microswitch inside the lock case is activated when the
knob/lever is rotated. The switch signals the use of that
opening to security systems allowing a non-disruptive
means of immediate egress. Specify L-Series lock case
with L283-263, or LV-Series lock case with L283-239.
L-Series RX Switch
black (common)
yellow
(NO)
blue
(NC)
LV-Series RX Switch
black
(common)
yellow
(NO)
blue
(NC)
Note: Locks shipped prior to mid-2010 are confi gured
with two-wire switches: L283-059 for normally closed or
L283-125 for normally open L-Series, and L283-197 for
normally closed or L283-196 for normally open LV-Series.
*Available on L and LV Series: L9080EL/EU, L9010,
L9050, L9060, L9070, L9071, L9076, L9077, L9080,
L9056, L9496, L9453, L9456, L9457, L9082 EL/EU
L9082 EL or EU Electrically Locked or Unlocked
Both Sides:
The same as L9080EL/EU, except both knobs/levers are
locked or unlocked simultaneously. (Previously XL11-452).
Cylinders:
All Schlage cylinders are available with the previously
mentioned locks. Specify the locks with the required
cylinder code, e.g. L9080PEL (code P) for classic and
full size Everest cylinders. For a complete list of order
codes, see "Ordering Procedures" on page 137.
Replacement Kit:
L283-053 Solenoid and Driver, EL or EU.
Electrical Requirements:
Voltage: 24V AC or 24V DC (max. 26V, min. 22V).
Peak Current: 1.3 Amps at 5 to 10 second intervals.
Holding Current: .135 Amps between peak current
intervals.
Operating Temperature: Max +151° F, Min. -31° F.
RX Microswitch: 5 Amps, normally closed circuit.
Typical Installation:
All installations should be in accordance with local
electrical codes and National Electrical Code NFPA #70.
It is recommended that each lock have its own 24 volt
transformer. Two or more locks may be operated in paral-
lel from a single transformer provided it has the neces-
sary current rating. DO NOT connect locks in series from
a higher voltage rated transformer. Damage to locks may
occur if they connect to a supply circuit that also contains
electromagnetic devices. The transient voltage must be
suppressed at the equipment producing them before
connecting the locks to a circuit. A varistor rate at 35
volts (at peak current) may be used for transient voltage
protection.
Solenoid
Operated
Lock
Frame to
Door Connector
(not furnished)
Install
varistor
here
if used
(not furnished)
Transformer
(not furnished)
Switch
(not furnished)
24V AC
110V AC