18-CD35D1-1 31
INSTALLER’S GUIDE
NOTE:
The manifold pressure must be referenced to
the burner box. The burner box pressure tap
equalizes the gas valve pressure regulator.
Manifold pressure is checked by installing a
tee (field supplied) in the tubing, between the
tee coming from the burner box tube and the
gas valve, in addition to the regular gas valve
pressure tap on the outlet side of the gas valve.
See Figure 55.
▲
CAUTION
!
Replace manifold pressure tap threaded plug and
leak check after checking/ adjusting manifold gas
pressure.
Table 19 lists the main burner orifices used with the furnace. If a
change of orifices is required to correct the furnace input rating.
Refer to Table 20.
TABLE 17
FINAL MANIFOLD PRESSURE SETTINGS
MODEL
FUEL
PRESSURE
NATURAL GAS
LP GAS
M951P040BU24AA
3.5" W.C.
11.0" W.C.
M951P060BU36AA
3.5" W.C.
11.0" W.C.
M951P080BU42AA
3.5" W.C.
11.0" W.C.
M951P100CU48AA
M951P100DU60AA
3.5" W.C.
11.0" W.C.
M951P120DU60AA
3.3" W.C.
11.0" W.C.
M951P040BD24AA
3.5" W.C.
11.0" W.C.
M951P065BD42AA
3.0" W.C.
9.5" W.C.
M951P085CD48AA
3.5" W.C.
11.0" W.C.
M951P110DD60AA
4.5" W.C.
11.0" W.C.
4. Turn on system power and energize valve.
5. Adjust gas heat by removing the adjustment regulator
cover screw.
a. To increase outlet pressure, turn the regulator adjust
screw clockwise.
b. To decrease outlet pressure, turn the regulator adjust
screw counterclockwise.
c. Adjust regulator until pressure shown on manometer
matches the pressure specified in Table 17.
1. The input of no more than nameplate rating and
no less than 93% of the nameplate rating, unless the
unit is derated for high altitude.
d. Replace and tighten the regulator cover screw
securely.
6. Cycle the valve several times to verify regulator setting.
a. Repeat steps 5-6 if needed.
7. Turn off all electrical power to the system.
8. Remove the manometer and flexible tubing and tighten
the pressure tap screw.
9. Using a leak detection solution or soap suds, check for
leaks at the pressure outlet boss and pressure tap test
screw.
10. Turn on system power and check operation of the unit.
▲
WARNING
!
SAFETY HAZARD
Replace and/ or tighten all plugs removed or
loosened when adjusting gas pressure. Leak
check the fittings before placing the furnace into
regular service. Failure to follow this warning
could result in fire, explosion, or property damage.
T