Ingersoll-Rand EAC180-300AK Installation & Operation Manual Download Page 17

Installation

RT-SVX052A-EN

17 

If the unit is not equipped with an optional factory 
installed nonfused disconnect switch, a field supplied 
disconnect switch must be installed at or near the unit 
in accordance with the National Electrical Code (NEC 
latest edition).

Location of the applicable electrical service entrance is 
illustrated in 

“Dimensional Data,” p. 8

. Complete the 

unit’s power wiring connections onto either; the main 
terminal block HTB1 inside the unit control panel, the 
factory mounted nonfused disconnect switch (UCD), or 
the electric heat terminal block. Refer to the customer 
connection diagram that shipped with the unit for 
specific termination points.

Provide proper grounding for the unit in accordance 
with local and national codes.

Optional TBUE Wiring (Through the Base 
Electrical Option)

Location of the applicable electrical service is 
illustrated below. Refer to the customer connection 
diagram that is shipped with the unit for specific 
termination points. The termination points, depending 
on the customer option selected would be a factory 
mounted nonfused disconnect switch (UDC).

Provide proper grounding for the unit in accordance 
with local and national codes.

Control Power Transformer

The 24-volt control power transformers are to be used only 
with the accessories called out in this manual. 
Transformers rated greater than 50 Vac are equipped with 
internal circuit breakers. If a circuit breaker trips, turn “Off” 
all power to the unit before attempting to reset it.

The transformer is located in the control panel. The circuit 
breaker is located on the left side of the transformer and 
can be reset by pressing in on the black reset button.

Controls using 24 Vac

Before installing any connecting wiring, refer to 

“Dimensional Data,” p. 8

 for the electrical access locations 

provided on the unit and 

Table 2, p. 17

 for AC conductor 

sizing guidelines.

1.

Use copper conductors unless otherwise specified.

2. Ensure that the AC control wiring between the controls 

and the unit’s termination point does not exceed three 
(3) ohms/conductor for the length of the run.

Note:

Resistance in excess of 3 ohms per conductor 
could cause component failure due to insufficient 
AC voltage supply.

3. Be sure to check all loads and conductors for grounds, 

shorts, and mis-wiring.

4. Do not run the AC low voltage wiring in the same 

conduit with the high voltage power wiring.

5. Route low voltage wiring per illustrations on

 

the next 

page.

Figure 13.

Through the base electrical option

NOTICE: 

Use Copper Conductors Only! 

Unit terminals are not designed to accept other types of 
conductors. Failure to use copper conductors could 
result in equipment damage. 

Table 2.

Electromechanical thermostat 24 Vac 
conductors

Distance from Unit to 

Control 

Recommended Wire Size

000–460 feet

18 gauge

000–140 m

0.75 mm

2

461–732 feet

16 gauge

Summary of Contents for EAC180-300AK

Page 1: ...ing Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on t...

Page 2: ...icates a potentially hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could r...

Page 3: ...r contact a qualified service organization with qualified experienced HVAC technicians to properly diagnose and repair this equipment WARNING Proper Field Wiring and Grounding Required All field wirin...

Page 4: ...tions 20 Unit Disconnect FIYUDC 20 Pre Start 21 Verifying Proper Air Flow Units with Belt Drive Indoor Fan 21 Electromechanical Controls Test Procedure 21 Start Up 22 Economizer Start Up 22 Compressor...

Page 5: ...halpy 0 100 without Barometric Relief4 F Economizer Reference Enthalpy 0 100 with Barometric Relief1 4 G Economizer Comparative Enthalpy 0 100 without Barometric Relief4 H Economizer Comparative Entha...

Page 6: ...o fieldadjustments andthe module willautomatically reset from a fault condition Discharge Line Thermostat Control The high pressure controls and discharge line thermostats are wired in series between...

Page 7: ...rom forming inside the unit s electrical compartments and motors if The unit is stored before it is installed or The unit is set on the roof curb and temporary heat is provided in the building Isolate...

Page 8: ...8 RT SVX052A EN Dimensional Data Figure 1 Typical installation clearance for single and multiple unit applications 5 8 5 0...

Page 9: ...RT SVX052A EN 9 Dimensional Data Figure 2 Cooling with optional electrical heat units overview Figure 3 Cooling with optional electrical units front side views 15 25 tons standard efficiency...

Page 10: ...52A EN Dimensional Data Figure 4 Cooling with optional electrical heat units plan view 15 25 tons standard efficiency Figure 5 Foundation units back view horizontal configuration 15 25 tons standard e...

Page 11: ...ndard efficiency Figure 7 Downflow duct connections field fabricated 15 25 tons standard efficiency 9 1 25 4 MM CURB FLANGE LONG SIDES SHORT SIDES Notes Duct flanges mount 7 7 16 down inside the curb...

Page 12: ...onal Data Figure 8 Downflow unit clearance 15 25 tons standard efficiency Figure 9 Barometric relief and economizer 15 25 tons standard efficiency MOTORIZED DAMPER BAROMETRIC RELIEF IS FOR USE WITH A...

Page 13: ...RT SVX052A EN 13 Dimensional Data Figure 10 Manual damper 15 25 tons standard efficiency...

Page 14: ...438 357 416 54 37 25 EAC300A 2208 1888 664 457 345 422 53 35 a Weights are approximate Horizontal and downflow unit and corner weights may vary slightly b Weights do not include additional factory or...

Page 15: ...rs gaskets must be installed around the curb perimeter flange and the supply and return air opening flanges General Unit Requirements The checklist listed below is a summary of the steps required to s...

Page 16: ...ion which could result in condensate backup due to air lock Filter Installation Each unit ships with 2 inch filters installed The quantity of filters is determined by unit size Access to the filters i...

Page 17: ...anual Transformers rated greater than 50 Vac are equipped with internal circuit breakers If a circuit breaker trips turn Off all power to the unit before attempting to reset it The transformer is loca...

Page 18: ...life If the voltage imbalance isover 2 percent notify the proper agencies to correct the voltage problem before operating this equipment Electrical Phasing Three Phase Motors The compressor motor s an...

Page 19: ...e the following checklist in conjunction with the general checklist General Unit Requirements p 15 to ensure that the unit is properly installed and ready for operation Check all electrical connection...

Page 20: ...ty found on the unit nameplate and the N E C 4 Route low voltage class II control wiring through hole in base of unit but not through high voltage conduit Feedcontrolwiringthroughbushingprovided on si...

Page 21: ...0 using the setpoint potentiometer located on the Economizer Control ECA if applicable Electromechanical Controls Test Procedure See unit schematic for correct wire numbers Fan Test and Minimum Ventil...

Page 22: ...ning a compressor interchange any two leads at the compressor Terminal block to check the internal phasing Refer to the following illustration for the compressor terminal phase identification Do not a...

Page 23: ...ocedures outlined in the previous sections i e operating the unit in each of its modes through all available stages of cooling and heating perform these final checks before leaving the unit Program th...

Page 24: ...s number represents the force in pounds required to give the needed deflection 6 Compare the force scale reading Step 5 with the appropriate force value listed in Table 5 p 24 If the force reading is...

Page 25: ...6 p 26 If the operating pressures indicate a refrigerant shortage measure the system superheat For guidelines refer to Compressor Start Up p 22 Note Do NOT release refrigerant to the atmosphere If add...

Page 26: ...nks provided 1 Complete Unit Model Number _____________________________________________________ 2 Unit Serial Number _____________________________________________________ 3 Wiring Diagram Numbers from...

Page 27: ...nit operations down Unit Economizer Control ECA Verify Economizer Status by Economizer Actuator ECA LED indicator OFF No Power or Failure ON Normal OK to Economize Slow Flash Normal Not OK to Economiz...

Page 28: ...low Schematic Type Voltage Diagram Number Description Constant Volume Power 208 230 380 2313 2202 EAC180 300 EAD180 300 60Hz Cooling only Electric Heat Control 208 230 380 2313 2207 EAC180 300 EAD180...

Page 29: ...may also have other rights which vary from state to state Trane 2701 Wilma Rudolph Blvd Clarksville TN 37040 1008 Attention Manager Product Service GW 602 4800 This warranty is for commercial usage of...

Page 30: ......

Page 31: ......

Page 32: ...portfolio of advanced controls and HVAC systems comprehensive building services and parts For more information visit www IRCO com The manufacturer has a policy of continuous product and product data...

Reviews: