Ingersoll-Rand D110IM User Manual Download Page 6

Installation & Commissioning

EN

3 Installation & Commissioning

3.1 Recommended system layout

The dryer should be installed with the correct pre-filtration and condensate management equipment to meet both the specification and local 
environmental requirements.

Referring to diagram A4 in Annex A, the following equipment is recommended to meet these requirements:

3.2 Locating the equipment

Identify a suitable location for the equipment taking into consideration the minimum space  requirements for maintenance and lifting equipment. 
When considering the final location of the equipment take into account the noise generated when in use.

The dryer can be free standing or secured to the floor via the fastener points provided in the base..

3.3 Mechanical Installation

Once the dryer has been located into position install the piping and filtration for connection to the inlet and outlet manifold. HE grade filter is 
required at the dryer inlet and a DP grade filter at the outlet as shown in diagram A5 of Annex A.

Ensure that each filter condensate drain is suitably piped away and any effluent is disposed of in accordance with local regulations.

 

The Energy Management System (EMS) system requires a sampling point to be inserted into the piping between the DP grade outlet filter and 
the isolation valve as shown in diagram A5. This sampling point should be linked to the 4mm push in connector of the EMS system using P.T.F.E 
tubing.

It is important to ensure that all piping materials are suitable for the application, clean and debris free. The diameter of the pipes must be 
sufficient to allow unrestricted inlet air supply to the equipment and outlet gas / air supply to the application.

When routing the pipes ensure that they are adequately supported to prevent damage and leaks in the system.

All components used within the system must be rated to at least the maximum operating pressure of the equipment. It is recommended that the 
system be protected with suitably rated pressure relief valves.

A by-pass line may be installed into the system to provide a constant air supply during maintenance. 

Only competent personnel trained, qualified, and approved by Ingersoll Rand should perform installation, commissioning 
and service procedures.

Ref

Description

Ref

Description

1

Compressor

6

DP Filter

2

Wet air receiver

7

Dryer

3

Bypass Line

8

GP Filter (optional)

4

Isolation Valves

9

Outlet to application

5

HE Filter

The use of a bypass line will allow wet untreated air into the system. It should therefore only be used in extreme 
circumstances.

Ref

Description

Ref

Description

1

HE grade filter

4

Isolation Valves

2

DP grade filter

5

Feed line

(Optional with Energy Management System)

3

By-pass line

6

GP grade filter (Optional)

The by-pass line will allow untreated air to pass to the application and should only be used when the dryer has been shut 
down.

Summary of Contents for D110IM

Page 1: ...EN USER GUIDE Original Language NL DE FR FI SV NO DA EL ES PT IT PL SK CS ET HU LV LT RU SL TR MT Desiccant Air Dryer D41IM D299IM...

Page 2: ...an extended warranty tailored service contracts or training on this equipment or any other equipment within the Ingersoll Rand range please contact your local Ingersoll Rand office Details of your nea...

Page 3: ...rough the regenerating column Energy Management System EMS optional If EMS is fitted this will adjust the dryer s cycle in line with the moisture loading placed upon it by constantly monitoring the pr...

Page 4: ...CRN OH0373 9C D41IM D150IM OH0372 9C D180IM D299IM CSA 173682 LR56310 Before continuing with the installation and commissioning of this equipment Ensure that it is correctly sized for the inlet pressu...

Page 5: ...f the dryer are as follows Remove the equipment from its packaging as shown in A2 in Annex A of this user guide and check that it has not been damaged in transit if so please contact your shipping com...

Page 6: ...his sampling point should be linked to the 4mm push in connector of the EMS system using P T F E tubing It is important to ensure that all piping materials are suitable for the application clean and d...

Page 7: ...ctrical power supply inlet on the equipment and connect to the electrical supply If a cordset other than the one provided with the equipment is used to connect the equipment to the electrical supply e...

Page 8: ...ention is required for normal operation Energy Management System EMS optional If the dryer is producing air at a better dewpoint than specified the EMS system will hold the dryer at a point just befor...

Page 9: ...al Component Operation Daily 3 month 6 month 12 month 24 month 30 month Dryer Check POWER ON indicator is illuminated Dryer Check STATUS FAULT indicators located on the controller Dryer Check for air...

Page 10: ...erhaul D41IM D110IM 38455713 1 Kit Valve Overhaul D150IM D299IM 38455747 1 E AA 11 2 Litre Bag 38455754 See table below MS 13X 11 2 Litre Bag 38455762 See table below Kit Column Seals D41IM D110IM 384...

Page 11: ...Servicing EN 5 4 Service Record Date of Commissioning Service Hours Date Serviced By Print Sign Comments Observations 4 000 8 000 16 000 20 000 24 000 28 000 32 000 36 000 40 000...

Page 12: ...r is not functioning correctly Test that condensate drain is operating correctly Check that the cooling water system is functioning correctly and that the water temperature is within specification wat...

Page 13: ...ccordingly Contact Ingersoll Rand for details on particle counting and air quality air measurement The compressor is not functioning correctly Check the documentation supplied by the compressor manufa...

Page 14: ...86 39 86 D71IM 1168 46 0 302 11 9 284 11 2 1125 44 29 352 13 86 44 97 D90IM 1333 52 5 302 11 9 284 11 2 1290 50 79 352 13 86 49 108 D110IM 1499 59 0 302 11 9 284 11 2 1456 57 32 352 13 86 54 119 D150...

Page 15: ...Troubleshooting EN A2 A3 D41IM D110IM D150IM D299IM...

Page 16: ...Troubleshooting EN A4 A5...

Page 17: ...gem den Bestimmungen der oben genannten Richtlinien Unterschrift Datum 11 10 07 Nummer der Erkl rung 00156 111007 D claration de conformit FR Ingersoll Rand Company Ltd Swan Lanne Hindley Green WIGAN...

Page 18: ...73 23 EEC 89 336 EEC 93 68 EEC 92 31 EEC Normas utilizadas EN ISO 12100 1 2003 EN ISO 12100 2 2003 EN 6100 6 1 2001 EN 61000 6 2 2001 EN 61000 6 3 2001 EN 61000 6 4 2001 EN 61000 3 2 2000 EN 61000 3 3...

Page 19: ...noven v e uveden ch sm rnic Podpis Datum 11 10 07 6 slo prohl en 00156 111007 Vastavusdeklaratsioon ET Ingersoll Rand Company Ltd Swan Lanne Hindley Green WIGAN WN2 4EZ UK Desiccant Air Dryer D41IM D5...

Page 20: ...9900792 5 Poobla 3eni zastopnik H Seddon Direktor za kakovost Ingersoll Rand Company Ltd Izjava Kot poobla eni zastopnik izjavljam da so zgornji podatki glede dobave proizvodnje tega izdelka skladni...

Page 21: ...or other items or conditions of products shall be in accordance with Ingersoll Rand Standard Terms and Conditions of Sale for such products which are available upon request Product Improvement is a co...

Reviews: