Operating ranges
Operating range cooling only
Outdoor temperature 0 - 115°F (-18.0 - 46°C)
Operating range heat pump
Outdoor temperature 5°F - 75°F (-15.0 - 24°C)
Connection piping requirements
9
Wall Unit
NOTICE
Maximum length of connecting piping is shown in the following table. While placing the units confirm that
the distance in between them exceeds the maximum length of connection piping.
NOTES:
1. Connecting piping must be covered with waterproof insulating material.
2. Tubing thickness 0.5-1.0 mm (0.02-0.04 in): bearing pressure 3.0 MPa
3. Shorter lengths of connecting tubing produce higher thermal efficiency and therefore it is preferable to reduce connection tubing
lengths whenever possible.
4. See oil trap instructions on page 21 for specific requirements when there exists a height difference superior to 20 feet between
the indoor unit and the outdoor unit.
Heat Pump
4TXK2309
4TXK2312
4TXK2318
4TXK2324
4TXK2330
4TXK2336
4MXW2309
4MXW2312
4MXW2318
4MXW2324
4MXW2330
4MXW2336
Refrigerant charge (oz.)
45.9
47.6
56.44
77.6
84.66
91.71
Standard length m (ft)
7.5 (25) 7.5 (25) 7.5 (25) 7.5 (25)
7.5 (25) 7.5 (25)
Additional refrigerant charge (oz/
ft) for larger length of piping as
compared to standard piping
0.2 0.2 0.2
0.5
0.5
0.5
Outside diameter
Liquid pipe
mm (in)
Φ
6.0 (1/4")
Φ
6.0 (1/4")
Φ
6.0 (1/4")
Φ
6.0 (1/4")
Φ
6.0 (1/4")
Φ
6.0 (1/4")
Gas pipe
mm (in)
Φ
9.52 (3/8")
Φ
12 (1/2")
Φ
16 (5/8")
Φ
16 (5/8")
Φ
16 (5/8")
Φ
16 (5/8")
Maximum distance
Height m
(ft)
10 (33) 10 (33) 10 (33) 10 (33)
10 (33)
10 (33)
Length m
(ft)
15 (49) 20 (66)
25 (82) 25 (82)
30 (98)
30 (98)
Pipe minimum length m (ft)
3 (10) 3 (10) 3 (10) 3 (10)
3 (10)
3 (10)
Cooling only
4TYK2309
4TYK2312
4TYK2318
4TYK2324
4TYK2330
4TYK2336
4MYW2309
4MYW2312
4MYW2318
4MYW2324
4MYW2330
4MYW2336
Refrigerant charge (oz.)
45.9
47.6
56.44
81.1
84.66
84.66
Standard length m (ft)
7.5 (25) 7.5 (25) 7.5 (25) 7.5 (25)
7.5 (25)
7.5 (25)
Additional refrigerant charge (oz/
ft) for larger length of piping as
compared to standard piping
0.2 0.2 0.2 0.2
0.2
0.2
Outside diameter
Liquid pipe
mm (in)
Φ
6.0 (1/4")
Φ
6.0 (1/4")
Φ
6.0 (1/4")
Φ
6.0 (1/4")
Φ
6.0 (1/4")
Φ
6.0 (1/4")
Gas pipe
mm (in)
Φ
9.52 (3/8")
Φ
12 (1/2")
Φ
16 (5/8")
Φ
16 (5/8")
Φ
16 (5/8")
Φ
16 (5/8")
Maximum distance
Height m
(ft)
10 (33) 10 (33) 10 (33) 10 (33)
10 (33)
10 (33)
Length m
(ft)
15 (49) 20 (66) 25 (82) 25 (82)
30 (98)
30 (98)
Pipe minimum length m (ft)
3 (10) 3 (10) 3 (10) 3 (10)
3 (10)
3 (10)
Compressor oil used
DAPHNE FVC50K
FVC68D/RB68EP
RB68EP RB68EP
PVE
FV50S
Compressor oil used
DAPHNE FVC50K DAPHNE FVC50K RB68EP
RB68EP
PVE
FV50S