Evaporator Fan Performance
8
RT-SVF28F-EN
Table 6.
Direct drive evaporator fan performance - 10 tons with standard efficiency gas heat - YSC120F3,4,W*H high
heat downflow airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
cfm
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm
bhp
rpm
bhp
3200 1055 0.70 1082 0.79 1109 0.87 1132 0.93 1156 1.01 1180 1.09 1205 1.17 1228 1.25 1252
1.33
1275
1.41
3600 1180 0.98 1205 1.07 1229 1.16 1252 1.25 1272 1.33 1293 1.40 1315 1.49 1337 1.59 1358
1.68
1379
1.77
4000 1305 1.32 1328 1.42 1350 1.52 1372 1.63 1392 1.73 1410 1.80 1429 1.89 1448 1.99 1468
2.09
1488
2.19
4400 1432 1.73 1452 1.84 1473 1.96 1493 2.07 1512 2.19 1530 2.29 1547 2.38 1564 2.47 1581
2.57
1599
2.68
4800 1558 2.22 1577 2.34 1596 2.47 1615 2.59 1633 2.72 1650 2.84 1667 2.96 1683 3.06 1698
3.15
—
—
continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm
bhp
rpm
bhp
3200 1298 1.49 1322 1.59 1348 1.69 1374 1.81 1398 1.91 1421 2.00 1443 2.10 1465 2.20 1488
2.30
1511
2.41
3600 1400 1.86 1421 1.95 1441 2.04 1462 2.14 1483 2.24 1507 2.36 1530 2.48 1552 2.61 1574
2.72
1594
2.83
4000 1507 2.29 1526 2.39 1544 2.49 1563 2.59 1582 2.69 1601 2.79 1619 2.90 1639 3.01 1657
3.13
1678
3.26
4400 1617 2.79 1635 2.91 1652 3.02 1669 3.13 1687 3.23
—
—
—
—
—
—
—
—
—
—
4800
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Notes:
1. For Direct Drive Evaporator Fan Speed (rpm), reference
.
2. Data includes pressure drop due to standard filters and wet coils.
3. Refer to
to determine additional static pressure drop due to other options/accessories.
4. Direct Drive Fan Motor Heat (MBH) = 2.8623xFan BHP -0.1504
5. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously
at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or
premature motor failure. Our product's warranty will not be affected.
Table 7.
Direct drive evaporator fan performance - 10 tons standard efficiency with gas heat - YSC120F3,4,W*H high
heat horizontal airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
cfm
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm
bhp
rpm
bhp
3200 1054 0.72 1084 0.79 1112 0.86 1141 0.95 1168 1.04 1193 1.12 1218 1.20 1242 1.28 1266
1.38
1289
1.48
3600 1179 1.00 1205 1.08 1231 1.16 1256 1.24 1282 1.35 1306 1.45 1329 1.54 1352 1.63 1374
1.72
1395
1.82
4000 1304 1.35 1328 1.44 1352 1.53 1375 1.62 1397 1.71 1420 1.83 1442 1.94 1463 2.04 1484
2.14
1504
2.24
4400 1429 1.78 1452 1.88 1474 1.98 1495 2.07 1515 2.17 1536 2.27 1556 2.40 1577 2.53 1597
2.64
1616
2.75
4800 1555 2.29 1576 2.40 1596 2.51 1616 2.61 1635 2.72 1654 2.82 1673 2.93 1692 3.07
—
—
—
—
continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm
bhp
rpm
bhp
3200 1314 1.57 1338 1.65 1362 1.74 1385 1.84 1407 1.93 1430 2.02 1453 2.12 1477 2.22 1498
2.32
1521
2.44
3600 1416 1.92 1436 2.03 1458 2.14 1480 2.24 1501 2.33 1522 2.43 1543 2.54 1563 2.64 1583
2.74
1604
2.85
4000 1524 2.35 1543 2.46 1562 2.56 1581 2.68 1600 2.80 1619 2.93 1638 3.04 1658 3.15 1677
3.26
1695
3.37
4400 1635 2.87 1653 2.97 1671 3.09 1689 3.21
—
—
—
—
—
—
—
—
—
—
—
—
4800
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Notes:
1. For Direct Drive Evaporator Fan Speed (rpm), reference
.
2. Data includes pressure drop due to standard filters and wet coils.
3. Refer to
to determine additional static pressure drop due to other options/accessories.
4. Direct Drive Fan Motor Heat (MBH) = 2.8623xFan BHP -0.1504
5. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously
at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or
premature motor failure. Our product's warranty will not be affected.