Evaporator Fan Performance
RT-SVF28F-EN
7
Table 4.
Direct drive evaporator fan performance - 10 tons standard efficiency with gas heat - YSC120F3,4,W*L,M low
& medium heat downflow airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
cfm
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm
bhp
rpm
bhp
3200 1055 0.73 1081 0.81 1105 0.88 1128 0.94 1152 1.01 1177 1.09 1202 1.17 1225 1.25 1249
1.33
1273
1.42
3600 1181 1.02 1204 1.10 1226 1.19 1248 1.27 1268 1.34 1289 1.42 1311 1.50 1333 1.59 1355
1.68
1376
1.77
4000 1307 1.38 1328 1.47 1348 1.56 1368 1.65 1388 1.74 1406 1.82 1425 1.91 1444 2.00 1464
2.10
1483
2.20
4400 1433 1.82 1453 1.92 1472 2.02 1490 2.12 1508 2.22 1525 2.32 1542 2.40 1559 2.49 1577
2.59
1594
2.69
4800 1560 2.34 1578 2.45 1595 2.56 1613 2.67 1629 2.77 1646 2.89 1662 2.99 1677 3.09 1692
3.18
—
—
continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm
bhp
rpm
bhp
3200 1296 1.51 1319 1.61 1343 1.70 1366 1.81 1390 1.91 1415 2.02 1438 2.11 1461 2.21 1484
2.31
1506
2.41
3600 1397 1.86 1418 1.95 1439 2.05 1460 2.16 1480 2.27 1501 2.38 1522 2.49 1543 2.61 1564
2.72
1585
2.83
4000 1503 2.30 1522 2.39 1542 2.49 1561 2.60 1579 2.70 1598 2.81 1616 2.93 1635 3.05 1654
3.17
1673
3.29
4400 1612 2.80 1630 2.91 1647 3.02 1665 3.13 1683 3.24 1700 3.34
—
—
—
—
—
—
—
—
4800
-
-
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Notes:
1. For Direct Drive Evaporator Fan Speed (rpm), reference
.
2. Data includes pressure drop due to standard filters and wet coils.
3. Refer to
to determine additional static pressure drop due to other options/accessories.
4. Direct Drive Fan Motor Heat (MBH) = 2.8623xFan BHP -0.1504
5. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously
at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or
premature motor failure. Our product's warranty will not be affected.
Table 5.
Direct drive evaporator fan performance - 10 tons standard efficiency with gas heat - YSC120F3,4,W*L,M low
& medium heat horizontal airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
cfm
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm
bhp
rpm
bhp
3200 1043 0.70 1072 0.78 1099 0.85 1128 0.94 1154 1.02 1179 1.10 1203 1.17 1227 1.26 1250
1.35
1274
1.44
3600 1166 0.98 1192 1.06 1217 1.14 1241 1.23 1267 1.33 1291 1.42 1314 1.51 1335 1.59 1356
1.68
1378
1.78
4000 1290 1.32 1314 1.41 1337 1.50 1359 1.60 1381 1.69 1404 1.80 1426 1.91 1447 2.01 1467
2.10
1486
2.20
4400 1415 1.73 1436 1.83 1458 1.94 1478 2.04 1498 2.14 1518 2.25 1539 2.37 1560 2.49 1579
2.60
1597
2.70
4800 1540 2.23 1560 2.34 1579 2.45 1598 2.56 1617 2.67 1635 2.79 1653 2.90 1672 3.03 1692
3.16
—
—
continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm
bhp
rpm
bhp
3200 1298 1.53 1323 1.63 1347 1.72 1370 1.82 1394 1.92 1416 2.02 1437 2.12 1459 2.22 1482
2.33
1503
2.43
3600 1398 1.88 1419 1.98 1440 2.08 1462 2.19 1484 2.30 1505 2.40 1527 2.52 1547 2.62 1568
2.74
1587
2.84
4000 1505 2.30 1524 2.41 1542 2.51 1562 2.63 1581 2.74 1600 2.85 1619 2.97 1639 3.09 1658
3.20
1677
3.32
4400 1615 2.81 1633 2.91 1650 3.02 1667 3.14 1685 3.26 1700 3.38
—
—
—
—
—
—
—
—
4800
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Notes:
1. For Direct Drive Evaporator Fan Speed (rpm), reference
.
2. Data includes pressure drop due to standard filters and wet coils.
3. Refer to
to determine additional static pressure drop due to other options/accessories.
4. Direct Drive Fan Motor Heat (MBH) = 2.8623xFan BHP -0.1504
5. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously
at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or
premature motor failure. Our product's warranty will not be affected.