INSTALLATION INSTRUCTIONS

This heater must be permanently installed and hard wired by a licensed electrician in accordance with local electrical 
codes. Assembly procedure must be performed with no electrical power to unit.

Step 1:

 Check UL/CUL/CE label on heater for proper voltage.

Step 2:

 Follow supplied wiring instructions. (See wiring instructions below)

Step 3:

 Heater must be mounted with reflector angled down.

Step 4:

  All electrical connections must be in compliance with the National Electric Code (NEC) and local codes for 

outdoor wiring.

Step 5:

 Use only wiring components UL/CUL/CE listed for outdoor use with IPX4 minimum rating.

3

WIRING INSTRUCTIONS

The heater is drilled and threaded for standard 1/2" conduit fittings. The installing electrician will need to provide the 
appropriate rigid metallic, flexible or liquid tight conduit for the installation location.

• Observe local electrical code regulations.
• Remove cover plate from junction box.
• Attach conduit.
• Use only copper wire suitable for 90°C.
• Replace cover plate. 

Connect power with flexible 
conduit or appropriate cord to 
allow heater to be swiveled.

Junction Box on top of the heater 
has a gasket side access cover.

The Junction Box inlet hole is 
sized for a standard ½” weather 
tight conduit fitting and has a 
locknut located on the inside of 
the box for fastening.

GREEN GROUND 

WIRE SCREW

TYPICAL WIRING OPTIONS

HEATING ELEMENT

OFF

ON

OFF

ON

HEATER

TOP

P L1

L2

H2

H1

HEATER

FOR 115V. PILOT 

LIGHT IF USED

11/32" (0.9 CM) INSIDE NUT

SNUG TO CERAMIC

11/32" (0.9 CM) OUTSIDE NUT

REAR VIEW OF

CONTROLLER FOR

MAX. 15 AMP

LOAD ONLY

"TOP" MARKED ON
REAR OF CONTROL

MUST BE INSTALLED

IN AN UP POSITION

240 V.

240 V.

WHITE

BLACK

115 

V.

TYPICAL 120V WIRING

FOR A SINGLE POLE SWITCH

TYPICAL 240V WIRING FOR 

A TWO POLE SWITCH

WIRING FOR OPTIONAL 120V/240V CONTROLS

Summary of Contents for C Series

Page 1: ...VE THIS MANUAL FOR FUTURE REFERENCE TABLE OF CONTENTS Warnings 2 Installation Instructions 3 Wiring Instructions 3 Mounting Instructions 4 Replacement Element Installation 5 Replacement Parts 5 Heater Coverage Areas 6 General Notes 6 Maintenance Instructions 6 Trouble Shooting 7 Location Suggestions 7 Warranty 8 ...

Page 2: ...d as UL CUL Listed from floor while heater is set at a downward angle of 30 to 60 degrees For Ceiling Mounting do not install heater closer than 18 45 7cm from adjacent walls and 6 15 2cm from ceiling and do not install less than 6 1 8m if the heater is labeled as UL Listed and 8 2 4m if the heater is labeled as UL CUL Listed from floor while heater is at a maximum 30 degrees Adjacent Heaters to b...

Page 3: ...allic flexible or liquid tight conduit for the installation location Observe local electrical code regulations Remove cover plate from junction box Attach conduit Use only copper wire suitable for 90 C Replace cover plate Connect power with flexible conduit or appropriate cord to allow heater to be swiveled Junction Box on top of the heater has a gasket side access cover The Junction Box inlet hol...

Page 4: ...inimum clearance is maintained around the heater on all four sides and 36 91 4cm directly in front A minimum of 6 15 24cm of clearance provided by mounting brackets is required behind the plane of the face Heater can be hung using chains or custom brackets Heater must be level but can be rotated around its horizontal axis Heater must be installed with the quartz tube horizontally level For maximum...

Page 5: ...eplacement elements for your Infratech heatingsystem pleasecontact usviaphoneorvisitourwebsite Consultthe labelonbackof heaterforproperwatts voltage andreplacementelementpart number REPLACEMENT ELEMENTS OTHER VOLTAGES ALSO AVAILABLE PART NUMBER ELEMENT NUMBER LENGTH WATTS VOLTS FITS 10 1020 E 7512 16 1 2 0 4m 750 120 C 7512 10 1050 E 1412 30 0 8m 1500 120 C 1512 10 1055 E 1424 30 0 8m 1500 240 C 1...

Page 6: ...egulator This low cost controller which is actually an infinite switch gently pulses the heat on and off at regular intervals when not on full power Dual Element Heaters can be wired with our Duplex Stack Switch which enables the ability to turn on and off each element independently providing for half power full power capabilities For ideal comfort heat the best solution is to heat from two sides ...

Page 7: ...TING Unless heaters are installed over 12 3 7m high it is generally recommended that all radiant heaters be mounted on an angle to assure that radiant warmth is distributed from the sides rather than straight down on the heads and shoulders of the people being warmed LOCATION SUGGESTIONS Angle fixture 30º to 60º from horizontal face down Best angle is approximately 45º Install fixture to heat the ...

Page 8: ... is not responsible for consequential or incidental damages Under no circumstances shall INFRATECH or any of its representatives be held liable for injury to any person or damage to any property however arising Important Please retain original proof of purchase to establish warranty period Any implied warranties of merchantability and fitness applicable to the equipment are limited in duration to ...

Reviews: