The warning “Warning! Parallel Firmware Error” will appear in current event
when the parallel setting is enabled, but the firmware does not support this
feature.
The way to release this warning is to turn off the AC power source and shut
down the system. After the system shutdown completely, turn on the AC
power to restart the UPS.
Table 4-10: Setup-Pre-Alarm setting list
Setting Item Sub Item
Explanation
Line Voltage
Range
--
Set line voltage range:
Upper limit
+5%
+10%
+15%
+20% (Default)
Lower limit
-5%
-10%
-15%
-20% (Default)
Line
Frequency
Range
--
Set line frequency range:
Upper / Lower limit
+/- 1Hz
+/- 2Hz
+/- 3Hz
+/- 4Hz (Default)
Load
--
Set UPS Overload percentage (40~100%)
100% (Default)
Set UPS load unbalance percentage (20~100%)
100% (Default)
Table 4-11: Setup-Parallel setting list
Setting Item Sub Item
Explanation
UPS Parallel --
Set UPS parallel
Disable (Default)
Enable
Independent
Battery
--
Set Independent Battery
Disable (Default)
Enable
4.2.7 Information Screen
In INFORMATION menu, you can check the serial number, firmware versions, system
configuration and settings of the UPS. The INFORMATION has the submenus, Identification,
System and Battery, as shown in Figure 4-28, 4-29.