Mode
Disable (Default)
Enable
MUST be reviewed after UPS installation.
If you need the Bypass power when UPS is OFF, please
enable it.
Auto-Restart --
Set auto-restart
Disable
Enable (Default)
After “Enable” is set, once UPS shutdown occurs due to
low battery and then utility restores, the UPS will return
to line mode.
Cold Start
--
Set cold start
Disable
Enable (Default)
After “Enable” is set, the UPS can be turned on without
connecting to utility by pressing Battery Start Button.
Refer to cold start operation for the details.
Battery
Mode Delay
Time
--
Set system shutdown delay time in battery mode
(0~9990sec).
0: Disable (Default)
Not 0: Enable
When this feature is enabled, UPS will shut off output
after UPS operates in Battery mode for certain seconds.
System
Shutdown
Time
--
Set system shutdown time (0.2~99min)
0.2 min (Default)
This delay time will start counting when the
CONTROL-Shutdown Restore command is executed.
System
Restore
Time
--
Set system restore time (0~9999min)
1 min (Default)
This delay time will start counting after shutdown time is
elapsed when the CONTROL-Shutdown Restore
command is executed.
Redundancy --
Set total power and redundancy
Total Power: the QTY of Power Modules
Redundancy: the QTY of redundant power module
MUST be set after UPS installation or the QTY of
Power Module is changed
Charger Test --
Set charger test
Disable (Default)
Enable
4.2.6.3 Setup-Battery Screen
Use UP and DOWN buttons to switch different sub-menus. Press ENTER button to go into the
BATTERY setting screen, as shown in Figure 4-24, 4-25.