INFOSEC UPS SYSTEM - 4, rue de la Rigotière – 44700 Orvault – FRANCE - www.infosec.fr
Hot Line: tel : + 33 (0)2 40 76 15 82 - fax : + 33 (0)2 40 94 29 51 - [email protected] - 09 05 04 205 12
60
9
Introduction – E
4
5000(S)/6000(S)/10000(S)
9.1
General specifications
Model E
4
5000 E
4
5000S E
4
6000 E
4
6000S E
4
10000 E
4
10000S
Power rating
5KVA/3,5KW
6KVA/4.2KW
10KVA/7KW
Frequency (Hz)
50
Voltage (176-276)VAC
Input
Current
25A max
31A max
50A max
Voltage 240VDC
Battery
Current
20A max
24A max
40A max
Voltage 220VAC
Output
Current 23A 27A 45A
Dimension (WxDxH) mm
260x570x717
Weight
(kg)
90 35 90 35 93 38
9.2
Electrical Performance
Input
Tension Frequency
Power
factor
Single-phase 46Hz-54Hz
>0.98
(full
load)
Output
Voltage
Regulation
Power
Factor
Frequency
tolerance
Distorsion Overload
capacity
Current
crest ratio
±
1% 0.7
lag
Synchronized
46-54Hz in Line
mode (AC mode)
±
0.1% of normal
frequency in
BATTERY mode
THD<2%
Full load
(Linear Load)
105%-130% load transfers to
bypass mode
after 10 minutes
>130% load transfers to
BY-PASS mode after 1 second
and shutdown the output after
1 minute
3:1 maximum
9.3
Operating Environment
Temperature Humidity Altitude
Storage temperature
0
°
C-40
°
C <95% <1000m 0
°
C-40
°
Note: if the UPS is installed or used in a place where the altitude is above than 1000m, the output
power must be reduced
in use, please refer to the following:
Altitude (M)
1000
1500
2000
2500 3000 3500 4000 4500 5000
Decrease in power
100% 95%
91% 86% 82% 78% 74% 70% 67%