2-4. UPS Installation for a Parallel System
If the UPS is only available for single operation, you may skip this section to the next.
1)
Install and wires the UPSs according to the section 2-3.
2)
Connect the output wires of each UPS to an output breaker.
3)
Connect all output breakers to a major output breaker. Then this major output breaker will directly connect to the
loads.
4)
Each UPS is connected to an independent battery pack.
NOTE:
The parallel system cannot use one battery pack. Otherwise, it will cause system permanent failure.
5)
Refer to the following wiring diagram: