6. Specifications
E4 LCD TT
10K (S)
E4 LCD TT
15K (S)
E4 LCD TT
20K (S)
E4 LCD TT
30K (S)
10 kVA / 8 kW
15 kVA / 12 kW
20 kVA / 16 kW
30 kVA / 24 kW
INPUT
Voltage
3 Phase + Neutral 380/400/415 V
Low voltage
range
Battery mode
transfer
230 V
(P/N)
176 VAC ± 3% at 100% load / 110 VAC ± 3% at 50% load
Low line
comeback
230 V
(P/N)
186 VAC at 100% load / 120 VAC at 50% load
High voltage
range
Battery mode
transfer
230 V
(P/N)
276 VAC ± 3% at 100% load / 300 VAC ± 3% at 50% load
High line
comeback
230 V
(P/N)
266 VAC ± 3% at 100% load / 290 VAC ± 3% at 50% load
Frequency range
46~54 Hz at 50Hz / 56~64 Hz at 60Hz
Phase
3-phase with neutral and ground
Power factor
≧
0.99 at 100% load
OUTPUT
Voltage
3 Phase + neutral 380/400/415 V
AC voltage regulation
± 1%
Frequency range (synchronized range)
46 ~ 54 Hz at 50 Hz / 56 ~ 64 Hz at 60 Hz
Frequency range (battery mode)
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current crest ratio
3:1 max
Harmonic distortion
≦
2% THD (linear load) /
≦
5% THD (nonlinear load)
Transfer time
AC mode to battery mode
Zero
Inverter to Bypass
Zero (when phase lock fails, <4ms interruption occurs from inverter to bypass)
Inverter to Eco mode
<10 ms
Waveform Pure
sine
wave
Backup time
From 5 to 45 minutes depending on connected load
EFFICIENCY
AC mode
89%
90%
Battery mode
86-88%
89%
BATTERIES
Standard
Model
Battery type
12 V / 9 AH
Number
20
(adjustable 18-20)
2 x 20
(adjustable 18-20)
3 x 20
(adjustable 18-20)
Recharging time
9 hours recover to 90% capacity
Charging current (max.)
1.0 A ± 10%
2.0 A ± 10%
2.0 A ± 10%
4.0 A ± 10%
Charging voltage (max.)
273 VDC ± 1%