Air inlet are designed at the bottom
and the rear of the UPS, whereas air
outlet are located on the top of the
unit : it is therefore useless to leave a
lateral clear-distance.
Front face
3.4 Connection of Power Cables
CAUTION! Only authorized person has to install or maintain UPS / batteries.
The AC input of the UPS should be supplied by a separate line from the AC distribution board.
The input/output cables can be sized to suit the modules rating according to the table below.
The connections of the electric panel should be supplied by grounded outlet. Cables enter the UPS modules
via entry panels in the base of cabinet. All control cables should be screened and run in a separate trunking
to the power cables.
The input/output cables can be sized to suit the modules’ rating according to the table below.
NOMINAL CURRENT : Ampere / Recommended Cable Size (mm
2
)
BUS BAR CONNECTION
STUD SIZE
Input Mains
With full battery Recharge
Bypass / output
At full load
380V 400V 415V 380V 400V 415V
Battery
at min.
Battery
Voltage
UPS
POWER
(kVA)
A / mm
2
A
/
mm
2
A
/
mm
2
A / mm
2
A
/
mm
2
A
/
mm
2
A
/
mm
2
Input/Output
Cable
Terminations
U-V-W-N
Battery
Terminations
+ & -
10
22A / 6
20A / 6
19A / 6
16A / 6
15A / 6
14A / 6
28A / 6
16mm
2
Terminals
16mm
2
Terminals
15
32A / 6
30A / 6
28A / 6
23A / 6
22A / 6
21A / 6
41A / 10
16mm
2
Terminals
16mm
2
Terminals
20
43A / 10
39A / 10
37A / 10
31A / 10
29A / 10
28A / 10
55A / 16
16mm
2
Terminals
16mm
2
Terminals
30
64A / 16
59A / 16
56A / 16
46A / 10
44A / 10
42A / 10
82A / 25
35mm
2
Terminals
35mm
2
Terminals
40
85A / 25
78A / 25
73A / 25
61A / 16
58A / 16
56A / 16 110A / 35
M6
M8
60
128A / 35 117A / 35 109A / 35
91A / 25
87A / 25
84A / 25 163A / 50
M6
M8
80
168A / 50 160A / 50 154A / 50 121A / 35 115A / 35 111A / 35 220A / 70
M6
M8
100-120
256A / 70 234A / 70 218A / 70 182A / 70 174A / 70
168A / 70 326A/100
M8
M8
160
329A / 95 312A / 95 301A / 95 230A / 70 218A / 70
210A / 70 430A/120
M8
M8
200
357A /185 339A /185 327A /185 243A /150 230A /150 223A /150 560 /185
M8 M10
NOTES:
The neutral conductor should be sized for 1,5 times the output/bypass phase current.
The Earth conductor should be sized at 2 times the output/bypass conductor (this is
dependent on the fault rating, cable lengths, type of protection etc.) These
recommendations are for guideline purposes only and are superceded by local
regulations and codes of practice.
Figure 3-1
Installation Diagram
250
cm
PYRAMID