Menu and submenu items
MAIN MENU
SUBMENU
MEANING
MEASURES MENU
LD%: 050 030 060
Output load
OPV: 220 221 219 V
Output voltage
FREQU: 50.0 Hz
Output frequency
IPV: 240 230 226 V
Input voltages
BYP: 225 221 219 V
Bypass source voltages
IPI: 031 040 020 A
Ginput currents
BATT: 432 V 06.7A
Battery voltage and charge current
TEMP: 24 C
Cabinet inside heat
CHARGE LEVEL: 60%
Battery charge level
ENTER EXIT
Exit from submenu
ALARMS MENU
UPS STATUS
Valid alarm
000>DATE AND ALARM
Recorded log events
ENTER CLEAR LOG
Clearing log records
PARR.ERR.NR
Parallel control board error nr.
ENTER EXIT
Exit from submenu
INFORMATION MENU
SYNC :OK COMM :OK
Syncronization and comminication
POWER: 20000 VA
Output power of the UPS
VERSION : MC1XX
Version of UPS
FREQUENCY : PLL/XTAL
Frequency generation mode
ENTER EXIT
Exit from submenu
PASSWORD MENU
(password required )
System settings
ENTER EXIT
Exit from submenu
SETTINGS MENU
MODE:
Operation mode selection
UPS No :
UPS number selection
REMOTE :ENABLE
Remote access on/off
RESTART:ON/OFF
Mains restored setting
BYP.PROTECT ON
Bypass load protection
ENTER EXIT
Exit from submenu
COMMAND MENU
SOUND : ON/OFF
Sound alert on/off
ENTER B.TEST>432
Manuel battery test
ENTER <BYPASS>
Manuel bypass
ENTER:MODEM INIT
Modem settings
ENTER <BOOST>
Boost charge on/off
SIMULATION OFF
Simülation mode selection
ENTER EXIT
Exit from submenu
TIME MENU
TIME : 23 :15
time
DATE : 11-10-2001
date
SET HOURS: 11
Adjust hours
SET MINS : 38
Adjust minutes
SET DAY : 21
Adjust day
SET MONTH : 06
Adjust month
SET YEAR : 2001
Adjust year
ENTER <UPDATE>
Write new time and date
ENTER EXIT
Exit from submenu