GENERAL DESCRIPTION

The Series 700AV/T-S Power Processor is designed to supply reliable, clean regulated power to critical 

loads.  An efficient design with state of the art micro-processor controlled solid state devices provide 

immunity to all line disturbances.

The basic design consists of a three phase triple shielded isolation transformer with seven separate voltage 

taps per phase.  Output regulation is achieved by monitoring the input and automatically switching taps 

anytime the input line sags or surges.  The use of a triple shielded isolation transformer provides superior 

common mode and transverse mode noise attenuation.  Automatic switching occurs during current zero 

allowing noise free switches for both leading and lagging power factor loads that are connected to the 

Series 700AV/T-S.

MONITOR

Monitoring of the Series 700AV/T-S is simple, clean and effective. Three green light indicators are utilized 

to display “POWER ON”. These indicator lights are connected directly to the output (line to neutral for each 

phase) and indicate that the Series 700AV/T-S is operating properly with just a quick glance. 

The Series 700AV/T-S is also provided with “INPUT OUT OF RANGE” red indicating LEDs for each phase. 

If any phase of the input voltage source exceeds the spe10%, -15% from nominal, the appropriate 

phase LED is illuminated.  

In addition, a red “ALERT” light is provided as an over temperature indicator. If an over temperature 

condition exists, the “ALERT” light will illuminate and shut down the output. Over temperature thermal 

sensors are strategically located at critical points on the regulator assemblies and transformer. The main 

AC input circuit breaker must be turned off in order to reset the “ALERT” light.

OUTPUT VOLTAGE METERS

Two (2) digital output meters are provided. One monitors the 208/120 VAC output and the other monitors 

the 480/277 VAC output. Each meter monitors and displays Line-to-Line and Line-to-Neutral voltages. 

Minimum and maximum voltage values are recorded in EPROM. High and low output voltage limit alarms 

are programmable and a visual indication given if limits are exceeded.

PROTECTION

Protection is accomplished very effectively to minimize failures and the cost of repairs. A total of five major 

devices protect the Series 700AV/T-S.

1. The input is protected with an integrally mounted AC circuit breaker for abnormal current overloads

and provides a convenient means of disconnecting utility power.

2. The main transformer is protected by fuse links connecting the SCR regulators together, and are

designed to clear in the event that two or more SCR’s should fail.  This will prevent a transformer tap

short and the possibility of transformer failure.

3. Overtemp sensing devices are mounted at critical points on the SCR regulating assembly and the

main transformer.  When an overtemp condition exists the “ALERT” light will illuminate and hold until

the overtemp is corrected.  There are no automatic shut-off circuits for the “ALERT” condition.  The

main AC input breaker must be turned off in order to reset the “ALERT” light.

4. Each output of the Series 700AV/T-S is protected with an integrally mounted AC breaker for abnormal

current overloads and provides a convenient means of disconnecting power from the load.

Summary of Contents for Transtector 700 AV/T-S Series

Page 1: ...th Voltage Regulation 60 Hz Owners Manual Quad Output Power Conditioner for Novalis TX with ExacTRAC and OBI Options 160K i 60 Hz Model Front Access Design Important safety instructions save these ins...

Page 2: ...nary Installation 6 7 Weights BTU and Dimensions 7 Input Wire Size Grounding and Output Wiring 8 9 Installation 10 13 Bypass Switch 14 Start up and Operation 15 Preventive Maintenance 16 Performance C...

Page 3: ...t by replacing it in the original container if possible If the original container is not available it is recommended that all openings that lead internally into the unit are covered so that dust water...

Page 4: ...the output Over temperature thermal sensors are strategically located at critical points on the regulator assemblies and transformer The main AC input circuit breaker must be turned off in order to re...

Page 5: ...IONS CAUTION RISK OF ELECTRICAL SHOCK AND HIGH SHORT CIRCUIT CURRENT THE FOLLOWING PRECAUTIONS SHOULD BE OBSERVED WHEN WORKING ON THE UNIT 1 REmOvE wATChES RINgS OR OThER mETAL ObjECTS 2 USE TOOLS wIT...

Page 6: ...t the top Therefore it should be installed in a clean dry place with enough clearance to allow a free flow of air Allow a minimum of 36 in front of the 700AV T S for installation operation and mainten...

Page 7: ...DIMENSIONS 75 kVA 2 194 lbs 995 18 kg 5 115 10 230 34 5 w x 35 875 d x 76 h 87 63 cm x 91 12 cm x 193 04 cm Stated BTU s Hr is at 75kVA rated load 100 duty cycle Operational BTU s Hr is typically at...

Page 8: ...ut ground lug TA 250 max wire range 6 AWG 250 MCM one piece E Output is a 4 wire 5 including ground If four 4 current carrying conductors are used in a raceway the neutral is assumed to be current car...

Page 9: ...subject to local codes Verify with a local electrician inspector The unit is constructed using an isolation transformer and is considered to be a separately derived system It should be grounded in ac...

Page 10: ...i 60 Hz Power Conditioner Owners Manual 10 INSTALLATION CABINET OUTLINE FRONT VIEW BOTTOM VIEW 76 000 3 000 AIR INLET FRONT VIEW 562 x 1 000 34 500 OUTPUT CONDITIONED POWER INPUT OUT OF RANGE ALERT C...

Page 11: ...ACCESS AREA TOP INPUT OUTPUT OUTPUT FILTER OUTPUT TERMINATIONS AND CURRENT TRANSFORMERS REMOVABLE TOP PANEL PROVIDES ACCESS TO TRANSFORMER TERMINATION ACCESS AREA BOTTOM INPUT OUTPUT 14 000 6 895 23 0...

Page 12: ...0K i 60 Hz Power Conditioner Owners Manual 12 INSTALLATION continued CABINET OUTLINE RIGHT SIDE VIEW TERMINATION ACCESS AREA OPTIONAL SIDE OUTPUT 4 850 8 250 4 500 2 810 35 500 RIGHT SIDE VIEW AIR FLO...

Page 13: ...e load current is not to exceed 80 of the output breaker s rating and not to exceed the rated total current BOTTOM ACCESS WIRE RUN ROUTE SEPERATION PLATE OUTPUT METERS 70A 480V OUTPUT BREAKER 60A 480V...

Page 14: ...rs NORMAL MODE With the switch in the normal position the Series 700 AV T S will provide clean and regulated power to the critical loads The Series 700 AV T S should have the switch in the normal posi...

Page 15: ...n the main AC input breaker 5 Verify that the output voltage is within the specified range 6 Verify output phase rotation is correct 7 Turn the system off 8 Connect the loads one at a time and repeat...

Page 16: ...a blown SCR is suspected contact Transtector for service 3 A simple performance checklist has been developed for use in maintenance See Performance Checklist and check off items 1 7 4 After items 1 7...

Page 17: ..._Fan Connections______Transformer Connections 7 Exercise all circuit breakers ______Input Breaker______Output Breakers 8 Input Output Voltage Checks Adjust as Needed No Load Input No Load Output A B__...

Page 18: ...ITHIN THE ENCLOSURE OF THE POWER SUPPLY SYSTEM CAUTION MUST BE TAKEN WHEN WORKING WITH THE ENCLOSURE IT IS RECOMMENDED THAT ALL WORK BE PERFORMED BY QUALIFIED ELECTRICAL PERSONNEL ONLY Rick Ribbeck Ph...

Page 19: ...13789 13789 CONTROL RELAY 1 13696 13696 13696 13696 PILOT LIGHT RED ALERT 3 109054 109054 109054 109054 PILOT LIGHT GREEN A B C 3 107829 107829 107829 107829 PILOT LIGHT INPUT OUT OF RANGE 3 23943 239...

Page 20: ...or GOLD PLUS PLAN Factory servicemen are not included in this warranty This Warranty is in lieu of all other warranties expressed or implied The giving of or failure to adhere to any advice or recomme...

Page 21: ...21 1402 001 APPENDIX A RELATIVE DRAWINGS SCHEMATICS...

Page 22: ...ERIES 700A FRONT ACCESS CABINET OUTLINE COPPER BUS OUTPUT TERMINATIONS TO TOP CUSTOMER S INPUT CONNECTS INPUT CIRCUIT BREAKER TERMINATION ACCESS AREA TOP INPUT OUTPUT OUTPUT FILTER OUTPUT TERMINATIONS...

Page 23: ...ke ID 83835 036 20GA 075 14GA 048 18GA 105 12GA 060 16GA 135 10GA AIR FLOW RIGHT SIDE VIEW 4 750 2 812 4 500 8 250 FRONT AIR OUTLET 35 515 15 875 3 716 5 750 34 389 23 000 1 875 3 364 6 895 14 000 FRO...

Page 24: ...5 036 20GA 075 14GA 048 18GA 105 12GA 060 16GA 135 10GA TOP VIEW FRONT D CARLSON 1 18 2008 1 4 SCALE TOLERANCE THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF TRANSTECTOR ANY REPRODU...

Page 25: ...Wp min 1785 0 lbs x 0 85 1517 25 lbs Fp 0 45 x 2777 25 1249 76 lbs Vertical Force Fp 0 15 x 2777 25 416 58 lbs Moment Mo 33 00 x 1249 76 41242 08 in lbs Tension Fp x Cg V4 3213 6 lbs Corners a b 43 1...

Page 26: ...ming the process required in this manual Damage to the unit or personal harm could happen if proper precautions are not taken This symbol indicates that there is a risk of electrical shock if proper p...

Page 27: ...27 1402 001 NOTES...

Page 28: ......

Reviews: