160K(i) 60 Hz Power Conditioner | Owners Manual
22
CABINET LAYOUT
8.000
T.SZWAST
REVISED OUTPUT BREAKER, ADDED KNOCK-OUTS IN
TOP, RECREATED IN CADRA FOR POWERWAY DATA BASE
3/30/0908
4
3
ADDED OUTPUT METERS AND MOVED 125A OUTPUT
BREAKER
4/28/2008
D. CARLSON
2
UPDATED PRINT TO REFLECT ONLY NEUTRAL AND
GROUND OUTPUT BUS.
2/1/2008
D. CARLSON
1
CHANGED INPUT GROUND LUG AND CHANGED (1)
208V OUTPUT CIRCUIT BREAKER TO 150A.
D. CARLSON
1/21/2008
REV.
DESCRIPTION
DATE
BY
REVISIONS
OUTPUT METERS
(4)Ø.875 KNOCK-OUTS
4
60A 480V OUTPUT BREAKER
BOTTOM VIEW
R
36" CLEARANCE REQUIRED ON FRONT SIDE FOR SERVICE OF REGULATOR SECTION
LIFT OFF ACCESS PANELS REQUIRE COMMON HAND TOOL FOR ACCESS.
REAR PANELS MAYBE REMOVED TO DECREASE DEPTH. MUST BE REINSTALLED.
NOTE:
.060 = 16GA. .135 = 10GA.
.048 = 18GA. .105 = 12GA
.036 = 20GA. .075 = 14GA.
Hayden Lake, ID 83835
SUPERIOR SURGE SUPPRESSION
OUTPUT VOLTAGES: 120/208 VAC & 277/480 VAC
INPUT VOLTAGES: 208, 240, 480, OR 600VAC
8(BCDE)LNX-160K(i)-700AV/T-S
SERIES 700A FRONT ACCESS CABINET OUTLINE
COPPER BUS
OUTPUT TERMINATIONS
TO TOP)
(CUSTOMER'S INPUT CONNECTS
INPUT CIRCUIT BREAKER
TERMINATION ACCESS AREA
TOP INPUT/OUTPUT
OUTPUT FILTER, OUTPUT TERMINATIONS AND CURRENT TRANSFORMERS.
REMOVABLE TOP PANEL PROVIDES ACCESS TO TRANSFORMER,
TERMINATION ACCESS AREA
OPTIONAL SIDE OUTPUT
TERMINATION ACCESS AREA
BOTTOM INPUT/OUTPUT
SCALE 1 : 2
DETAIL A
AIR FLOW
1/18/2008
D.CARLSON
76.000
3.000
BYPASS SWITCH
AIR INLET
14.000
6.895
23.000
15.875
3.716
5.690
FRONT VIEW
4.850
8.250
4.500
2.810
35.500
RIGHT SIDE VIEW
LEFT SIDE VIEW
6.895
30.271
2.739
30.750
Ø.562 x 1.000
2.469
3.875
34.500
REAR VIEW
AIR FLOW
30A 120V OUTPUT BREAKER
150A 208V OUTPUT BREAKER
OUT OF RANGE & MONITOR ALERT LIGHTS
: 1:8
SCALE
TOLERANCE
3
OF
1
SHEET
PROHIBITED.
TRANSTECTOR IS
WITHOUT THE WRITTEN PERMISSION OF
REPRODUCTION IN PART OR AS A WHOLE
TRANSTECTOR. ANY
DRAWING IS THE SOLE PROPERTY OF
THE INFORMATION CONTAINED IN THIS
420196
.
.
MATERIAL:
REV
DWG. NO.
DATE
CHECKED
DRAWN
PROPRIETARY AND CONFIDENTIAL
"
A
70A 480V OUTPUT BREAKER
OUTPUT CONDITIONE
D POWER
INPUT OUT OF RANGE
ALERT
C
B
A
WIRE RANGE: 6 AWG - 250 MCM
INPUT GROUND LUG (1) TA 250
Summary of Contents for Transtector 700 AV/T-S Series