Technical Index 

 

Temperature Measurement Range 

-20 ~ 100 ºC 

Installation Method 

Insertion type, depth 50mm 

Signal Output 

RS485 

Protocol 

MODBUS 

Supply Voltage 

9 ~ 28 VDC 

Precision 

±1.5% FS 

Working Temperature (Host) 

-20 ~ 60 ºC 

Working Temperature (Probe) 

-20 ~ 100 ºC 

Protection Level 

IP65 

Direct Out 

RS485 

Red 

+Vcc 

Green 

RS485_A 

Black 

GND 

White 

RS485_B 

Shield 

Shield 

Electrical Connection Method  

 

Notes 

 

The temperature sensor probe is directly inserted into the measuring in any position 
(vertical, horizontal, inclined) and the connecting cable with the cable is inserted into 

the host. 

 

After opening the product packaging, please check the appearance of the product is 
intact. Verify the relevant content of the product manual is consistent with the product  

 

Strictly obey the wiring diagram of the product and work under the excitation voltage of 
the product, do not supply over voltage to the product.  

 

Do not hit / knock the product to avoid damage to the appearance and internal structure 
of the ring. 

 

The product has no self-repair parts for customers, please contact the company in case 
of any failure on 800.341.5266. 

MODBUS Communication Protocol 

The basic settings of the communication protocol: 

 

Transmission mode: MODBUS-RTU mode. 

 

Communication parameters: Default baud rate is 9600bps (optional 1200bps, 2400bps, 
4800bps, 9600bps, 14400bps, 19200bps, 28800bps, 38400bps, 57600bps, 115200bps, 

can be configured according to user requirements). 1 start bit, 8 data bits, none check, 

1 stop bit.  

 

Slave address: The factory default is 123 and can be configured according to user  
requirements. The universal slave address is 200 (Note: If a multi-machine  

communication network is formed, other slave addresses cannot be set to 200)

 