BSC-50D User Guide
16
4.7 User setup
Up to 20 SMS Users can be declared in a BSC-50D Unit. Only declared users can
interact (send, receive SMS) with the unit. BSC-50D features three levels of user rights.
The following options can be configured for each user:
1. User administration option. Status Messages are sent only to users with
Administration Rights.
2. Device configuration option. It represents the right to configure the BSC-50D Unit.
3. SMS Recipient option. It elects the user as SMS Recipient.
A new user can be created using the command:
0500,id,n,p,c1,c2,c3
0500: Command
ID
id:
1-20, User ID
n:
Up to 15 characters, User name
p:
Up to 15 characters, Phone number
c1:
0/1, User Administration Rights (0 for ‘No’ 1 for ‘Yes’)
c2:
0/1, Device Configuration Rights (0 for ‘No’ 1 for ‘Yes’)
c3:
0/1, Alarm SMS Recipient (0 for ‘No’ 1 for ‘Yes’)
c4:
0/1, M2M, User is a M2M device (0 for ‘No’ 1 for ‘Yes’)
Scope: COMM_MCU
4.7.1 Change User Configuration
0502,id,c1,c2,c3,c4
0502: Command
ID
id:
1-20, User ID
c1:
0/1, User Administration Rights (0 for ‘No’ 1 for ‘Yes’)
c2:
0/1, Device Configuration Rights (0 for ‘No’ 1 for ‘Yes’)
c3:
0/1, Alarm SMS Recipient (0 for ‘No’ 1 for ‘Yes’)
c4:
0/1, M2M, User is a M2M device (0 for ‘No’ 1 for ‘Yes’)
Scope: COMM_MCU
4.7.2 Delete a User
0501,id
0501: Command
ID
id:
1-20, User ID
Scope: COMM_MCU
4.8 Defining Event specific Alarm Recipients
Special commands are available to select the SMS Recipients for each Alarm Event. If
no specific Recipient list exists for an Alarm Event, then the corresponding SMS is
transmitted to all users with the SMS Recipient option checked. M2M Recipients will
receive the associated M2M Message, while Phone Recipients (M2P) will receive the
respective M2P Text Message (See 4.6).
4.8.1 DI Alarm Events
1103,n,id
1103: Command
ID
n:
1-4, DI number
id:
1-20, User ID