BSC-50D User Guide
13
4.5 Triggering a Rate change
Attention: If the Standby Mode is enabled, only DI or CNT Alarm Events can be used
for triggering!
4.5.1 Using Temperature alarm as Trigger
1207,n,lo,hi
1207:
Command ID
n:
1, AI number
lo:
0/1, Action on Low Alarm: 0
Ignore, 1
Trigger
hi:
0/1, Action on High Alarm: 0
Ignore, 1
Trigger
Scope: LP-MCU
4.5.2 Using a DI Alarm as Trigger
1107,n,ng,ps
1107: Command ID
n:
1-4, DI number
ng:
0/1, Action on a negative transition: 0
Ignore, 1
Trigger
ps:
0/1, Action on a positive transition: 0
Ignore, 1
Trigger
Scope: LP-MCU
4.5.3 Using a Counter Alarm as Trigger
1157,n,hi
1157: Command ID
n:
1, CNT number
hi:
0/1, Action on High Alarm: 0
Ignore, 1
Trigger
Scope: LP-MCU