CA1 is a room controller with one 0...10 V output or 3-point output. The unit is 

suitable for zone control of heating or cooling. It has a built-in sensor, input for 

external sensor and input for occupancy mode. The controller can operate in 

either P or PI mode. It also has an input for change-over, which controls whether it 

operates in heating or cooling mode.

Installation

Mount the controller in a place that reflects the overall ambient temperature in the 

room. Open the front cover by depressing the plastic latchhook on the lower cover 

edge.

Ambient  temperature, running 

0...+50°C

Ambient humidity 

 

 

max 90% RH

Protection class 

 

 

IP20

Wiring

Supply voltage

24 V AC ±15%, 50...60 Hz. Power consumption 2 VA.

Terminal 1 

24 V AC

Terminal 2 

24 V AC System neutral

Output 3-point

Terminal 3 

24 V AC (G+) actuator common 

Terminal 4 

3-point, increase 

Terminal 5 

3-point, decrease

Output 0...10 V

0...10 V DC, 1 mA. Load impedance min. 10 KOhm.

Terminal 6 

0...10 V DC

Terminal 7 

Signal neutral

Sensor

The controller has a built-in sensor. If an external sensor is used, the jumper Ext/

Int (BY1) should be set in Ext position.

Terminal 7 

Signal neutral  

Terminal 10 

Ext. sensor (NTC)

Occupancy mode control

The controller can be set to occupied or unoccupied mode:  

Open contact = occupied mode 

Closed contact = unoccupied mode

The base setpoint value is 22°C. It can be reset depending on the setting of the 

potentiometer ”Unoccupied”, and is adjustable with a span of ±6°C.

Terminal 7 

Signal neutral

Terminal 9 

Occupancy input

Change-over

The CA1 change-over function input can be used to automatically control the CA1 

mode of operation, i.e. heating or cooling function. Connect a sensor of type AB 

Industrietechnik NTC or a potential free shorting switch between this terminal and 

GND. Heating function is selected when terminal is shorted, and cooling function 

when left open.

If a sensor is used, it should have a 0..30°C range. The temperature at the sensor 

controls function. Mount the sensor so it monitors the supply water temperature. 

When this temperature exceeds 22°C, the output function will change to heating 

and if it drops below 18°C, the output function will change to cooling.

Note!

 For proper function when using a change-over sensor the system must 

have constant primary-water circulation.

 

If change-over is not used, the input 

terminal should be shorted to GND when heating function is desired and left open 

for cooling function. 

Room controller, one 0...10 V output or 3-point output

Terminal 8 

Change-over sensor or free shorting switch

 

Terminal 7 

Signal GND

Settings

Setpoint: 

Adjust with knob that extends from the lower right of the casing. The 

knob setting can be mechanically fixed with a latchscrew located under the front 

cover.

P-Band:

 

0.5...50 K (See figure 2)

Heating/Cooling function: 

See the section ”Change-over function” above.

Pot. unoccupied mode (Factory setting = 3 (25°C, 19°C))

Position  

0     1    2    3    4    5    6 

Cooling setp. 

22  23  24  25  26  27  28 °C

 

Heating setp. 

22  21  20  19  18  17  16 °C

Jumpers

Jumper BY1 

Right = Internal sensor (factory setting) 

 

Left = External sensor

Jumper BY2 

Closed = I-time is 2 min 

 

Open = I-time is 20 min 

(factory setting)

BY2 setting valid only when BY3 is set to PI-function.

Jumper BY3 

Closed = P-function 

 

Open = PI-function 

(factory setting)

Setpoint calibration

Should the setpoint need calibration the knob rim with the scale can be detatched 

from the hub and remounted in a new position. Grip across the rim and pull out at 

the same time as maintaining an inward pressure on the hub (see figure below). 

When remounting, make sure the parts snap together properly.

Indicators

CA1 has a green LED (PWR) which indicates supply power (see figure 2). There 

is also a red LED (H) which indicated heating/cooling function. If the LED is lit, 

the controller is set in heating function. If it is not lit, the controller is set in cooling 

function. Occupancy mode is indicated by a green LED (Occ). If this is lit, the 

controller is working in occupied mode. If it is not lit, the controller is working in 

unoccupied mode.

 EMC emissions & immunity standards

This product conforms to the requirements of the EMC Directive 2004/108/EC 

through product standards EN 61000-6-1 and EN 61000-6-3.

RoHS

This product conforms to the Directive 2011/65/EU of the European Parliament 

and of the Council.

Contact

AB Industrietechnik Srl

Via Julius Durst, 70 - 39042 Bressanone (BZ) - Italy

Tel.  +39 0472/830626 - Fax +39 0472/831840

www.industrietechnik.it - [email protected]

Fig 1. 

Measurements in mm

1
2
3
4
5
6
7

8

 

24 V AC supply
System neutral
24 V AC (G+) output, for actuator supply
3-point output increase
3-point output decrease
0…10 V DC control output
Signal neutral

Change-over input

Occupancy input
External sensor

10

Fig 2.

11870 MA

Y 14

BY2 BY3

BY1

P-band

PWR

Unocc. mode

Occ

H

IMPORTANT: Read these instruc-

tions before installation and wiring 

of the product

INSTRUCTION

  

INSTRUCTION

  

Summary of Contents for CA1

Page 1: ...si desidera la funzione di riscaldamento lasciato invece aperto per la funzione di raffreddamento Regolatore della temperatura ambiente con una uscita 0 10 V o con uscita a 3 punti Morsetto 8 Sensore per commutazione o contatto libero da potenziale Morsetto 7 Comune GND Impostazioni Setpoint eseguire la regolazione con la manopola di regolazione presente sul lato destro della custodia L impostazio...

Page 2: ...d be shorted to GND when heating function is desired and left open for cooling function Room controller one 0 10 V output or 3 point output Terminal 8 Change over sensor or free shorting switch Terminal 7 Signal GND Settings Setpoint Adjust with knob that extends from the lower right of the casing The knob setting can be mechanically fixed with a latchscrew located under the front cover P Band 0 5...

Page 3: ...hange over Fühler muß das System konstante Vorlauftemperatur haben Wenn der change over nicht gebraucht wird ist die Klemme für heizen mit GND zu verbinden und für kühlen offen zu lassen Raumregler mit 0 10V Ausgang oder 3 Punktausgang Klemme 8 Change over Fühler oder Schließerkontakt Klemme 7 Signal GND Einstellungen Sollwert Stellt man mit dem Drehrknopf unten rechts am Gehäuse ein Er kann mit e...

Page 4: ... avec la sonde le système doit présenter une circulation en circuit primaire en permanence Si la fonction d inversion n est pas utilisée l entrée reste ouverte lorsque le régulateur a une Régulateur d ambiance sortie 0 10 V ou 3 points fonction de refroidissement L entrée est court circuitée lorsque le régulateur a une fonction de chauffage Borne 8 Sonde de change over ou contact de travail Borne ...

Reviews: